Reset & cancel: Furnace tips (part 2 of 2)
Short, practical technician tips on reset & cancel for furnace. Check each one against the manual for your exact model before acting.
Reset a soft lockout (R95P)
Rheem · R95PA040, 060, 070 (1317MSA), R95PA085, 100 (1521MSA), R95PA115 (1524MSA); (-)95P series
Soft lockouts can be cleared by cycling the heat call or power. A 1-hour lockout also resets on its own after one hour; a hard lockout (code 93) needs a power reset; code 61 hard lockout can be reset by cycling the heat call.
- Cycle the heat call off for 2 to 20 seconds, or cycle power
- Code 93 hard lockout: cycle power
Reset the overtemperature safety switch
Rheem · All 96V and 96MDV series furnaces
The overtemperature switches sit in the burner compartment and trip when combustion air is inadequate. A tripped switch must be reset by hand, but only after the cause is cleared.
- Find the cause of the overtemperature trip, usually inadequate combustion air.
- Correct the cause.
- Press the manual reset on the switch in the burner compartment.
Burner box temperature limit reset
Trane · All models
A manual reset temperature limit is on the burner box and opens the gas circuit on overheat.
- If the limit trips, find and correct the overheat cause.
- Reset the manual limit on the burner box.
- For full shutdown, set the main gas valve switch to OFF and disconnect electrical supply.
Burner box temperature limit shutdown
Trane · AUH1B furnaces
The manual reset limit on the burner box opens and shuts off gas flow when temperature is excessive.
- Check vent and combustion air inlet terminations for blockage.
- Clear any blockage, then press the reset button.
- If there is no blockage, have a qualified servicer reset the limit.
Reset after lockout
Trane · AUH1B furnaces
The control stays locked out until it is reset manually.
- Turn system power off, on, off, then on again within 30 seconds.
- Reset can be done at the unit power source or at the thermostat.
- If the sequence is not completed within 30 seconds, it will not reset.
Reset the control to factory defaults
Trane · S8V2, S8B1, S8X1, S8X2
Holding Menu and Option together at idle resets all menu values to factory defaults; the display flashes FD three times to confirm.
- Make sure the display is in idle (IdL)
- Hold Menu and Option together for 15 seconds, then release
- FD flashes three times
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.