Other: Furnace tips (part 6 of 8)
Short, practical technician tips on other for furnace. Check each one against the manual for your exact model before acting.
Horizontal installation: external condensate trap and clamps
Rheem · Horizontal left and right conversions
Horizontal installations require the condensate trap mounted externally below the unit. Mount the trap after the unit is at its installation point to avoid damage in transport. Hand-tighten screws when mounting the trap or drain coupling to protect the mounting flange. Allow at least 6 in. of clearance below the furnace. When horizontal, worm drive clamps on the flue transition or IDB couplings must sit above the level midline.
- Mount the trap externally below the unit after the furnace is in place.
- Hand-tighten the trap and drain coupling screws.
- Keep at least 6 in. of clearance below the furnace.
- Position worm drive clamps on the flue transition and IDB couplings above the midline.
- Apply freeze protection if required.
Humidifier output
Rheem · Humidifier accessory
The humidifier output is a set of dry contacts. Logic and wiring diagrams are in the Humidification/Dehumidification section.
- Wire the humidifier to the dry contacts as shown in the Humidification/Dehumidification section.
IDB coupling orientation
Rheem · Horizontal right with vertical vent conversion
If the IDB coupling is removed during conversion, it must go back in the right direction. The coupling has an arrow showing exhaust flow direction, and the arrow must point the correct way.
- Before reinstalling the IDB coupling, find the arrow on the coupling.
- Check that the arrow points in the direction of exhaust flow.
Indoor combustion air protection and exhaust fans
Rheem · Non-direct vent installations using indoor air
When indoor air is used for combustion, the inlet opening at the furnace must be protected from accidental blockage. Do not take air from a heated space with a fireplace, exhaust fan or other device that may cause negative pressure. If an exhaust fan is installed, provide enough ventilation to prevent negative pressure.
- Protect the furnace combustion air inlet from blockage.
- Do not draw indoor combustion air from spaces with fireplaces or exhaust fans.
- Provide enough ventilation to stop negative pressure from exhaust fans.
Install an auxiliary drain pan where damage could occur
Rheem · 96V and 96MDV series furnaces
Recognized codes recommend an auxiliary drain pan under the furnace and under any evaporator coil located where an overflow or blocked primary drain could damage the building or its contents.
- Install an auxiliary drain pan under the furnace and any evaporator coil in areas where water damage is possible.
Installation warnings for the cabinet and jacket
Rheem · All installations
Do not install the furnace on its back with access doors facing up. Do not lift the unit by the heat exchanger tubes, as this can damage the heat exchanger. Keep combustible materials, gasoline and other flammable vapors and liquids away from the furnace jacket. Do not use the furnace area as a storage or broom closet.
- Do not install the furnace on its back with access doors up.
- Lift the unit by the cabinet, not the heat exchanger tubes.
- Keep the area around the furnace clear of combustibles and flammable liquids.
Insulate vent in freezing spaces
Rheem · Vents through unconditioned spaces
Vents through unconditioned spaces where below-freezing temperatures are expected must be insulated with approved insulation. Armaflex or Rubatex may be used. Do not apply heat tape to the vent pipe. Un-insulated pipe can freeze and block the vent, preventing furnace operation.
- Insulate the vent through unconditioned space with approved insulation.
- Do not install heat tape on the vent pipe.
Integrated furnace control layout and key connections
Rheem · R96V two-stage communicating furnace control
Key items on the integrated furnace control: P1, P2 and P5 are factory-wired low-voltage harness connections. J1 (RJ-14) is for factory programming only. T1 is the spark ignition transformer (about 60 Hz, minimum 12 kV). P3 is the inducer output (120 VAC, high and low speed). T3 is the EAC output. P4 is the ECM blower communications connection. S1, S2 and S3 are dipswitch banks. S4 is the bias/termination dipswitch bank. U38 holds the TX (red) and RX (green) communications LEDs. S8 is the pushbutton. U38 also drives the dual 7-segment display. P6 is the memory card connector. Humidifier relay contacts are labeled HUM.
L1 and L2 polarity
Rheem · Line voltage connections
L1 (hot) and L2 (neutral) polarity must be correct. If they are reversed, the ignition control may not sense flame.
- Confirm L1 and L2 are not reversed when making field connections.
- If flame sensing faults after install, check line polarity first.
Leak checking gas connections
Rheem · All gas connections
Never use matches, flame or any ignition source to find leaks. Use an approved chloride-free soap and water solution or another approved detector. Repair any leak and check again.
- Apply approved chloride-free soap and water solution to each joint.
- Repair any leak and repeat the check.
- Never use a flame to check for leaks.
LP tank contamination warning
Rheem · LP gas supply
LP tanks, trucks and other delivery vessels must not hold anything but LP gas, such as fertilizer. Contamination can damage the furnace and voids the warranty. Confirm with the supplier.
- Confirm with the LP supplier that the tanks and vessels are used only for LP gas.
Massachusetts side-wall vent: CO detectors and warning sign
Rheem · Side-wall horizontally vented installations in Massachusetts
For side-wall horizontal vent terminations less than 7 ft above grade in Massachusetts homes, a hard-wired CO detector with battery backup must be on the floor where the furnace is installed, and a battery or hard-wired CO detector on each additional level. Detectors must meet NFPA 720 and ANSI/UL 2034 and be IAS certified. A metal or plastic sign at least 8 ft above grade, in line with the vent, must read GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS, with letters at least 1/2 inch. If the detectors cannot be installed at completion, the owner has 30 days, and a battery-operated CO detector must be installed in the meantime.
- Confirm a hard-wired CO detector with battery backup is on the furnace floor level.
- Confirm a CO detector is installed on each additional level served.
- Confirm the warning sign is mounted at least 8 ft above grade, in line with the vent terminal.
- Leave the installation manual and venting parts list with the appliance.
Model data card replacement
Rheem · 96V and 96MDV communicating furnaces
The model data card is wire-tied to the furnace and should only be removed when the control is replaced. Replacement cards are model specific.
- Keep the card with the furnace unless the control is being replaced
- Install the replacement card with the matching model data at connector P6
Natural gas at high altitude: derate
Rheem · Natural gas above 2,000 ft
No high altitude pressure switch changes are needed. Derate the input by 4% per thousand feet above 2,000 ft. Factory orifices are sized for 1100 BTU/ft3 at sea level; regional heating values may remove the need to change them except at extreme altitudes. Above 2,000 ft, follow local codes or NFGC/CSA B149.1.
- Derate the input 4% per 1,000 ft above 2,000 ft.
- Check the local gas heating value before changing orifices.
- Follow local codes, or NFGC / CSA B149.1 where no local code applies.
Never bypass safety switches
Rheem · 96V and 96MDV series furnaces
A safety switch that shuts the furnace down or makes it cycle intermittently points to a real hazard that a qualified technician must fix. Do not reset safety controls without correcting the cause and verifying safe operation.
- Do not jumper or remove any safety switch from the control circuit.
- Find and correct the cause before resetting any safety control.
- Replace safety control parts only with identical OEM parts.
Never operate the system without filters
Rheem · 96V and 96MDV series furnaces
Running without filters lets dust collect in the ducts and at the registers. Dust that reaches the heat exchanger chars and leaves soot on walls, ceilings and furnishings. Soot can also come from certain candles or untrimmed candlewicks.
- Install air filters before operating the system.
- Check that filters are in place at every startup.
Never operate without filters or panels
Rheem · R96V furnace
Running the system for long periods without filters lets dust collect in ducts and registers. Recirculated dust chars on the heat exchanger and soils the home. Replace all blower doors and compartment covers after servicing. Do not run the unit without all panels and doors in place.
- Install or confirm the filter before startup.
- Replace all blower doors and compartment covers after any service.
- Do not operate the furnace without all panels and doors secured.
Only current vent instructions apply
Rheem · All 96V and 96MDV series furnaces
Only the current vent instructions in this manual apply. All 90 Plus gas furnaces cannot be common-vented with any other appliance.
- Use the current vent instructions for the install.
- Do not common-vent this furnace with any other appliance.
Overheating or gas supply that will not shut off
Rheem · 96V and 96MDV furnaces
If the furnace overheats or the gas supply does not shut off, close the manual gas valve for the appliance before shutting off electrical power. Otherwise an explosion or fire can result.
- Close the manual gas valve for the appliance first.
- Then shut off electrical power.
Polypropylene vent products
Rheem · Polypropylene vent systems
Centrotherm Innoflue and DuraventPolypro single-wall and flex products are approved only for single appliance use. Do not exceed listed lengths, diameters or elbows. Use only the terminations listed in Tables 5 and 6. Liners for B-vent or chimney are for non-direct venting only. These products are listed in Canada under ULC-S636.
- Confirm the product and termination are listed in Tables 5 or 6.
- Check the vent length and elbow count against Table 4.
- Follow the manufacturer's instructions for installation.
Provide combustion and ventilation air
Rheem · 96V and 96MDV series furnaces
Combustion and ventilation air must be supplied as required by the National Fuel Gas Code (US) or CSA B149.1 (Canada) and by the combustion and ventilation air section of these instructions.
- Verify combustion and ventilation air provisions before startup.
- Follow the combustion air section of the manual for the installation type.
PVC solvent cement safety
Rheem · PVC vent joints
PVC and CPVC solvent cements and primers are highly flammable. Use good ventilation and do not assemble near a heat source or open flame.
- Ventilate the work area.
- Keep cement away from heat sources and open flames.
- Do not use cement that is curdled, lumpy or thick, and do not thin it.
Read the fault display correctly
Rheem · 96V and 96MDV communicating furnaces
Faults flash on for one second and off for half a second, and each fault is shown at least twice. Normal operating codes stay steady on. Check the display orientation first, because an upside-down display changes the reading.
- Confirm display orientation using dipswitch S1-1 before reading codes
- Note the code and any second code shown alternately with it
- Use the fault priority list to pick which fault shows when several are active
Recommended direct vent installation
Rheem · Venting type selection
Direct vent installations are recommended for better indoor air quality, added safety and performance. Non-direct installations must provide combustion air as set out in the National Fuel Gas Code and, in Canada, CSA B149.1.
- Use direct vent where practical.
- For non-direct, provide combustion air per NFPA 54 or CSA B149.1.
Recommended elbow count
Rheem · All vent runs
Exceeding the recommended maximum number of elbows can cause nuisance pressure switch operation. Long sweep elbows are preferred. Mixing elbow types is allowed, but standard 90s and 45s used alone at the maximum count may cause nuisance outages.
- Count elbows against the maximum in the Table 4 elbow column for the model.
- Use long sweep 90s wherever possible.
Remove the shipping base pan from the top of the unit
Rheem · All 96V and 96MDV series furnaces
The solid metal base pan must be taken off the top of the furnace before it is installed. If it stays in the shipping position it can damage the furnace or other equipment.
- Remove the solid base panel from the top of the unit before setting the furnace.
Residential garage installation height
Rheem · Furnaces installed in residential garages
In a residential garage, the burners and ignition source must be at least 18 inches (450 mm) above the floor to reduce the risk of igniting flammable vapors. The furnace must also be located or protected from physical damage by vehicles.
- Confirm burners and ignition source are at least 18 in. (450 mm) above the floor.
- Locate or guard the furnace to prevent vehicle damage.
Seal and install a base plate when the factory return is unused
Rheem · 96V and 96MDV series furnaces
If the factory return-air connection is not used, it must be sealed with a solid metal base plate. Otherwise carbon monoxide and other contaminants can be drawn into the conditioned air space. Factory base plates are sold as accessories; part numbers are in the furnace spec sheet.
- Install a solid metal base plate over the unused factory return connection.
- Seal the base plate and all return air duct connections.
Seal ducts and equipment where fumes or CO can migrate
Rheem · 96V and 96MDV series furnaces
Duct leaks can pull dirt, fumes, odors and carbon monoxide into the living space. Equipment or ducts in garages, storage areas or spaces with fuel-burning appliances must have all joints, seams and openings sealed.
- Seal all joints, seams and openings in equipment and ducts located in garages or storage areas.
- Seal equipment and ducts in spaces with water heaters or boilers to prevent depressurization and migration of combustion products.
Seal return air ducts when supply ducts leave the furnace space
Rheem · 96V and 96MDV series furnaces
If supply ducts carry air to areas outside the furnace space, the return air must also come through ducts sealed to the furnace casing and terminating outside that space.
- Seal return ducts to the furnace casing.
- Terminate return ducts outside the furnace space.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.