Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Network priority is set from the Master only

Weil-McLain · Multiple boiler networks on Evergreen Pro control

Each of the four inputs on the Master or any shadow boiler can be assigned as Network Priority 1 or 2, or Local Priority 1 or 2. Network priority settings are common to all boilers and can only be changed at the Master. When a Local Priority input closes, that boiler modulates from its own inlet and outlet sensors instead of being controlled by the Master.

  1. Make all Network Priority 1 and 2 changes at the Master boiler.
  2. Assign Local Priority inputs on the boiler that should respond to them locally.

Never common vent the ECO Tec with another appliance

Weil-McLain · ECO Tec Series 3 replacing a boiler on a common vent

The ECO Tec cannot share a common vent with any other appliance. When an old boiler is replaced, the ECO Tec must have its own vent and air piping. The remaining appliances on the old common vent may then be oversized and need to be checked.

  1. Do not connect the ECO Tec to an existing common vent.
  2. Install new vent and air piping as specified in this manual.
  3. Check the remaining appliances on the old vent for proper venting (see the vent verification guide).

Orifice sizing is critical; check the orifice table

Weil-McLain · EG 30-75 natural gas, including Canada altitude table

Only the orifices listed for the model and elevation may be used. Wrong orifices cause unsafe firing and property damage. The orifice drill-size table is printed on page 17 but its values did not extract clearly, so read it from the printed page.

  1. Confirm boiler model and altitude before selecting orifices.
  2. Use only the orifice drill size listed for that model and elevation (Table 5, page 17).

Outdoor reset and DHW mode

Weil-McLain · Zone valve and circulator zoning with DHW piping

Setting the control to DHW mode when the system is meant for space heating may violate Section 303 of the 2007 Energy Act. Exemptions are listed on page 137 of the manual.

  1. Do not override outdoor reset for a space heating system by selecting DHW mode.

Outdoor sensor and energy saving override

Weil-McLain · Ultra Series 4 boilers

The energy saving feature lowers boiler water temperature as the load drops. The override is only for specific cases.

  1. Install the outdoor sensor supplied with the boiler unless one of the listed exemptions applies.
  2. Do not use the override unless an external energy management system reduces water temperature with load, the boiler does no space heating, the boiler is part of a modular or multiple system of 300,000 Btuh or more, or the boiler has a tankless coil (not applicable to Ultra).

Outdoor sensor must be installed

Weil-McLain · ECO Tec Series 3 boilers

The outdoor sensor shipped with the boiler must be installed unless one of the exemptions applies.

Overheating or gas shutoff failure

Weil-McLain · All listed boiler series

If the boiler overheats or the gas supply does not shut off, the pump must stay powered.

  1. Do not turn off or disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location external to the appliance.

Overheating or gas supply fails to shut off

Weil-McLain · Ultra Series 4 boilers

If the boiler overheats or the gas does not shut off, do not cut power to the pump.

  1. Shut off the gas supply at a point outside the appliance.
  2. Leave the pump electrical supply on.

Overheating or gas supply that will not shut off

Weil-McLain · ECO Tec Series 3 operation

If the boiler overheats or the gas supply does not shut off, do not cut the power to the circulator. Shut off the gas at a location outside the appliance.

  1. Do not turn off or disconnect the electrical supply to the circulator in this case.
  2. Shut off the gas supply at a point outside the boiler.
  3. Do not block combustion or ventilation air to the boiler.

Piping connection sizes and required fittings

Weil-McLain · ECO Tec Series 3 piping

Pipe sizes and the fittings needed for the low water cut-off and air relief.

  1. Boiler water outlet and inlet (items 14 and 15): all heat only models and 199 Combi use 1 inch male NPT; 150 and 110 Combi use 3/4 inch male NPT.
  2. Install a tee for the low water cut-off (LWCO) at item 16.
  3. Gas line connection at item 17 is 1/2 inch male NPT.
  4. Air elimination/relief valve (item 38): 3/4 inch male NPT. Use a 3/4 inch tee and 3/4 inch street elbow for the relief valve. Connecting an automatic air vent to the top tee is recommended.
  5. Boiler drain valve (item 23) is shipped loose; pipe it on a reducing tee at the lowest point of the return piping.

Pressure/temperature gauge limit

Weil-McLain · Ultra Series 4 pressure/temperature gauge

Daily reading must stay at or below 25 psig. Call a technician if the problem persists.

  1. Read the pressure/temperature gauge daily.
  2. Confirm the pressure does not exceed 25 psig.
  3. If the reading stays high, contact a qualified service technician.

Priority MAX and MIN on-time behavior

Weil-McLain · SVF Series 1 priorities

MAX ON TIME limits how long a priority can run before a lower priority's call takes over. MIN ON TIME sets how long a priority must run before a higher priority or the next lower priority can take over. Inputs on the same priority run together when active.

  1. Set MAX ON TIME and MIN ON TIME for each priority in the Priority Switching settings.
  2. Set Blr Circ to OFF for DHW that is directly piped with its own DHW circulator.

Propane conversion requirement

Weil-McLain · Ultra Series 4 boilers

Ultra boilers must be converted for propane unless made for propane. Propane-ready models carry an LP suffix after the model number. All other models need conversion.

  1. Check the model number for an LP suffix.
  2. If there is no LP suffix, convert the boiler for propane using page 48 before operating.

Propane-ready and factory propane models

Weil-McLain · Ultra-80, 105, 155, 230, 299, 399 and 80LP

Ultra boilers ship ready for natural gas only, unless the model is propane-ready. Propane-ready units have LP after the model number. Ultra-80LP is factory-equipped for propane.

  1. Check the model suffix before firing on propane.
  2. For non-LP models other than Ultra-399, install the propane orifice or conversion kit before propane firing.
  3. Ultra-80 natural gas units needing a burner conversion must use the special-order conversion kit instructions, not this manual.

Protect exposed vent pipe from freezing

Weil-McLain · Direct vent terminations

Do not extend exposed vent pipe outside the building beyond the length shown in the manual. Condensate can freeze and block the vent.

  1. Keep exposed vent pipe outside the building within the length shown in the manual.
  2. Check that condensate cannot freeze and block the vent pipe.

Protect low-temperature circuits on multi-temperature systems

Weil-McLain · Multi-temperature heating systems on Series 2 boilers

If the system has both low-temperature and high-temperature circuits, the low-temperature circuits need their own limit controls. Without them, property damage can occur.

  1. Wire limit controls on each low-temperature circuit to an external limit circuit.
  2. Confirm the limit controls regulate those circuits before commissioning.

Protecting and capping the concentric termination during install

Weil-McLain · 3 in or 4 in concentric termination assembly

Blocked air passages will stop the boiler from running, and cemented parts cannot be repaired. Keep debris out during installation, and do not alter the assembly.

  1. Wrap plastic or other protection over the end of the exposed assembly before inserting it through the roof or wall.
  2. Do not cement the rain cap until the assembly is through the penetration and all supports are installed.
  3. After positioning, place the bird screen on the end of the inner pipe, then cement the rain cap in place.
  4. Do not cut or alter the termination assembly. A cut part cannot be cleaned and must be replaced.

ProTools app: clone settings and update software over Bluetooth

Weil-McLain · ECO Tec Series 3 boilers with Unity 2.0 control

The ProTools app connects over Bluetooth. Its clone-to-phone feature copies settings from one boiler to another, and it can also update the boiler software.

  1. Connect the phone to the boiler over Bluetooth using the ProTools app.
  2. Use clone-to-phone to copy settings from one boiler to another.
  3. Update the boiler software through the app to get the latest features.

Purchased items needed for termination

Weil-McLain · Sidewall and vertical terminations

Bird screens, the concentric termination kit and the 45-degree elbow for concentric runs are not supplied with the boiler and must be bought separately.

  1. Check parts before starting. Concentric kit needs a separate 45-degree elbow in the piping.
  2. Maximum vent and air lengths already include the 45-degree elbow allowance.

Read and save boiler configuration with WM ProTools

Weil-McLain · ECO Tec Series 3 boilers with WM ProTools app

The app can load, save and view the boiler configuration. Saved files are stored on the phone only, so uninstalling the app deletes them. Save the information for your records.

  1. In the app, choose READ/WRITE Configuration.
  2. Press READ Configuration and wait several seconds for the data to load.
  3. Review the information, then press Save Configuration.
  4. Enter a descriptive name and press Save.

Read software versions

Weil-McLain · Unity control, SVF Series 1

The SOFTWARE VERSIONS screen shows the display version, main micro and second micro.

  1. Open DIAGNOSTICS > SOFTWARE VERSIONS.
  2. Record DISPLAY, MAIN MICRO and SECOND MICRO versions.

Reinstall door and check gaskets after service

Weil-McLain · All Ultra Series 4 boilers

The boiler door must be sealed and fastened so the boiler does not draw air from the boiler room.

  1. Reinstall the boiler jacket front door after startup or service.
  2. Inspect the door gaskets; replace them if torn or gapped.
  3. Make sure the door is securely fastened.

Reinstall jacket door after servicing

Weil-McLain · ECO Tec Series 3 gas boilers

A properly sealed jacket door keeps the boiler from drawing air from the room.

  1. Reinstall the jacket door after start-up or service.
  2. Make sure it is securely fastened.
  3. Check the jacket door gaskets for tears or gaps and replace if needed.

Reinstall the jacket door after service

Weil-McLain · All ECO Tec Series 3 models

The jacket door must be fastened securely after start-up or any service so the boiler does not pull air from the boiler room. This matters most when other appliances share the room. Check the door gasket on the cabinet front. It must have no tears or gaps and should be replaced if damaged.

  1. Reinstall the jacket door after start-up or servicing.
  2. Confirm the door is fastened securely.
  3. Inspect the door gasket for tears or gaps and replace it if needed.

Relief valve and by-pass regulator piping

Weil-McLain · Express Setup Examples C and D piping

The relief valve is supplied with the boiler and must be field piped to the boiler In connection. Relief valve piping runs to a drain. A by-pass pressure regulator is required in zone valve systems.

  1. Pipe the supplied relief valve to the boiler In connection; see Figure 12 on page 18.
  2. Run relief valve discharge piping to a drain.
  3. In zone valve systems, install a by-pass pressure regulator.

Remote 0-10 VDC modulation input

Weil-McLain · Ultra U-Control remote modulation

The U-Control accepts a remote 0-10 VDC signal on P15 terminal 6 (positive) and terminal 5 (common). The boiler starts above 1.0 VDC, shuts off below 0.5 VDC, stays at low fire until 2.0 VDC, then increases firing rate up to full input at 10.0 VDC. The control still monitors temperatures using the Priority 1 settings.

  1. Connect the positive 0-10 VDC wire to P15 terminal 6.
  2. Connect the signal common to P15 terminal 5.
  3. Set the boiler as Type 4 (SHADOW) if a separate controller is providing the signal.

Replace flue gas temperature sensor after combustion test

Weil-McLain · All Ultra Series 4 models after combustion testing

A flue gas temperature sensor left out or badly seated can let flue gas spill into the boiler enclosure.

  1. Remove the rubber grommet from the probe.
  2. Insert the rubber grommet into the flue pipe.
  3. Insert the probe into the rubber grommet.
  4. Confirm the sensor is fully replaced before running the boiler.

Reset the maintenance reminder after service

Weil-McLain · Evergreen Pro Series 2 boilers

Resets the maintenance reminder to the next service date.

  1. Open SERVICE > SERVICE INFO.
  2. Select Reset Reminder.
  3. Confirm that the Last Maintenance and Next Due dates updated.

Rollout thermal fuse element has cut off gas flow

Weil-McLain · CGa, CGi, EG and PEG boilers

The rollout thermal fuse cuts gas flow if flame rollout occurs. The boiler must not be restarted until a service technician has checked it.

  1. Do not attempt to place the boiler in operation
  2. Call a service technician immediately

Rollout thermal fuse on EG-30 to EG-75

Weil-McLain · EG-30 through EG-75

The rollout thermal fuse element mounts on the front access panel for EG-30 through EG-75.

  1. Install the rollout thermal fuse element with the wire terminals facing up on the front access panel (Figure 40, page 49).
  2. Wire it per the appropriate wiring diagram.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.