Other: Boiler tips (part 40 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Circulator exercising
Weil-McLain · Evergreen Series 2 pump settings
After 72 hours of boiler inactivity, the selected circulator outputs energize briefly.
- Select the circulator outputs to exercise in Pump Settings.
Circulator LED status
Weil-McLain · Internal Taco 0015e3 circulator
The circulator LED shows its operating state. Orange means on, flashing white means air bound or cavitation, red means blocked, and off means the circulator is off.
- If the LED is flashing white, purge air from the system and check for cavitation.
- If the LED is red, check for a blockage in the circulator.
Circulator lubrication
Weil-McLain · Ultra Series 4 boilers and system circulators
The Ultra circulator is water-lubricated and needs no oil. Other circulators in the system may need oil.
- Do not oil the Ultra circulator; it is water-lubricated.
- Check other system circulators and oil only those that need it, following the circulator maker's instructions.
- Do not over-oil; over-oiling will damage the circulator.
Circulator output load limits
Weil-McLain · Output 1, 2 and 3 circulator and auxiliary loads
Each 120VAC pump output handles only 2.2 A. Larger circulators need a relay or starter, with only the relay coil wired to the boiler terminal.
- Check the circulator amp rating before connecting it to Output 1, 2 or 3.
- If the circulator draws more than 2.2 A, install a circulator relay or starter.
- Connect only the 120VAC coil to the boiler circulator terminals.
- Use an isolation relay if a device needs a different voltage or an isolated contact.
Clean the DHW external filter and combi manifold filters
Weil-McLain · Combi models for manifold filters; all models for the external inlet filter
Clean the domestic inlet water filter installed in the piping near the boiler, following the manufacturer's recommended cleaning procedure. On combi models, also clean the combi manifold DHW flow switch filter and the bypass filter. The DHW brazed plate should be cleaned annually, and more often if water quality requires it.
- Clean the domestic inlet filter in the piping near the boiler using the filter maker's procedure.
- On combi models, clean the DHW flow switch filter and bypass filter per page 157.
- Clean the DHW brazed plate annually per page 154, or more often for poor water quality.
Combi-only components
Weil-McLain · ECO Tec Series 3 Combi models
These parts are present only on Combi models (DHW side of the boiler).
- Brazed plate heat exchanger (item 33) transfers heat from boiler water to domestic water.
- DHW outlet temperature sensor (item 34) controls input based on how close the water is to set point.
- DHW 3-way valve (item 35) and actuator (item 36) route boiler water through the brazed plate or bypass it to the heating system.
- DHW flow sensor (item 37) starts the boiler and lets it modulate when flow of 0.5 GPM or more is detected.
- DHW inlet and outlet pipes (items 39 and 40): 199 uses 3/4 inch NPT; 150 and 110 use 1/2 inch NPT.
Combustion air and surge protection
Weil-McLain · ECO Tec Series 3 installation
Keep combustion air clean and protect the control from power surges.
- Do not place the combustion air intake where contamination of the combustion air is possible.
- Install surge protection on the boiler power supply to reduce the chance of control board damage.
Combustion air and vent piping rules at the boiler
Weil-McLain · ECO Tec Series 3 vent and air piping
The air inlet must be piped unless a Weil-McLain Direct Exhaust kit is used and its requirements are met. The air inlet connection at the boiler is 3" PVC only. The vent may use 3" PVC, CPVC, stainless or polypropylene, with approved adapters.
- Pipe combustion air to the boiler air intake, not a room air opening, unless using the Direct Exhaust kit.
- Use 3" PVC at the air inlet connection.
- Use a 3" transition at the boiler if running 2" pipe.
- Use only approved adapters; a PP adapter with its own seal that interferes with the boiler seal must not be used.
- Use a tapered reducer with a 3" PVC nipple (at least 6" long) for 3" to 2" transitions. Do not use a bushing.
- Use only the approved parts listed in the parts section (Figure 152, page 171).
Concentric termination warnings
Weil-McLain · Concentric sidewall termination
Do not alter or cut the concentric assembly. Blocked air passages stop the boiler, and a cut or altered assembly can allow flue gas recirculation and toxic emissions. Pipes must butt correctly at both ends to prevent recirculation.
- Shorten inner and outer pipes only if both still butt correctly at each end.
- Protect the exposed end of the assembly with wrap while it is fed through the wall to keep debris out.
- Use the maker's PVC adapter if connecting AL29-4C stainless vent to a PVC concentric attachment.
Condensate drain trap
Weil-McLain · ECO Tec Series 3 installation
The condensate trap is field installed and connects to the boiler condensate tube at the bottom of the boiler.
- Connect the field-supplied condensate drain trap assembly to the condensate tube at the bottom of the boiler (see installation section).
Condensate is acidic
Weil-McLain · All Ultra models with condensate drain
Condensate typically has a pH of 3.2 to 4.5. Install a neutralizing filter where local code requires it. The Weil-McLain neutralizer kit is listed in the replacement parts section.
- Check local code for neutralizer requirements.
- Fit the Weil-McLain neutralizing kit if required.
Condensate line requirements
Weil-McLain · SVF 1500-3000
Keep condensate flowing freely or the boiler can lock out.
- Use 3/4 in PVC or CPVC pipe to a drain or condensate pump.
- Use materials that meet ASTM D1785, F441 or D2665, and cement that meets ASTM D2564 or F493. In Canada use CSA or ULC certified pipe, fittings and cement.
- Keep the line clear so condensate cannot freeze or back up into the boiler.
- Expect acidic condensate (about pH 3.2 to 4.5); install a neutralizer where local code requires it.
- Keep the trap float in place to prevent flue gas leakage through the drain.
Control display navigation
Weil-McLain · Evergreen Pro control display
The Evergreen Pro display uses touch gestures.
- Swipe left or right to move forward and backward on applicable screens.
- Press icons on screen to perform the action shown.
- Place a finger on the slide bar empty space and hold to scroll, or swipe up or down on applicable screens.
- Double tap an editable parameter to enter edit mode.
- Note that screens shown in the manual are typical and vary with the control settings chosen.
Control display status screens
Weil-McLain · Evergreen Pro control display, Figure 9
The Status screen shows the active sequence of operation and its priority. Other display screens show live readings: 0-10V input value from an external device; inputs 1 to 4 with assignment, custom name and status; which aux/pump outputs are on; Additional Heat Demand on or off (only if a priority uses it); outdoor temperature (only if used); system supply and return temperatures (only if used); target temperature of the active priority; boiler out and boiler in temperatures; and blower modulation rate.
Control feature summary
Weil-McLain · ECO Tec Series 3 control
Options available in the control: PREHEAT (Off, Economy, High Performance), ECO BOOST (recharges boiler water once after a combi DHW draw), blower calibration (faster purge speeds), Fahrenheit or Celsius units, manual reset high limit, and daylight saving time.
- Select PREHEAT mode if faster combi DHW response is needed.
- Enable ECO BOOST if the burner should keep firing after combi flow ends to recover heat exchanger temperature.
- Use blower calibration to fine-tune purge speed if time to heat delivery is too long.
DHW piped in system: no DHW redundancy
Weil-McLain · Multi-boiler Example A piping (DHW directly connected)
When DHW is supplied from boiler 2 in a direct-piped layout, DHW is lost if boiler 2 is not running.
- Tell the owner that DHW can only be supplied when Boiler 2 is operational.
- Do not rely on this layout for DHW backup.
DHW priority setup
Weil-McLain · Direct connect and primary/secondary piping with DHW tank
Priority 1 is the default for DHW and turns off lower priorities during DHW calls. MAX ON TIME can limit that. Use Priority 2 or 3 for DHW if DHW should not take priority. Overriding outdoor reset by setting DHW mode for space heating may violate Section 303 of the 2007 Energy Act (see page 184 for exemptions).
- Wire the DHW aquastat to Input 1 and assign it to Priority 1 for DHW priority.
- On combi models, use INPUT2/PRIORITY 2 for an indirect DHW system.
- Adjust MAX ON TIME if the DHW priority call must be shortened.
- Do not set DHW mode to override outdoor reset on a space heating system.
DHW priority turns off space heating
Weil-McLain · Systems with indirect DHW tank
When DHW is priority 1, the U-Control turns off space heating and the boiler circulator during DHW heating. An optional timeout setting can override this. The flow/check valve on the boiler outlet stops gravity circulation during DHW heating.
- Set the DHW input to priority 1 when space heating should pause during DHW heating.
- Set the optional timeout if space heating must continue during DHW heating.
Direct vent air duct installation
Weil-McLain · SVF 1500-3000 Series 1, direct vent
For direct vent, combustion air is ducted directly from outside to the boiler air intake fitting. Sidewall or vertical direct vent options are available.
- Duct combustion air from outside directly to the boiler air intake fitting.
- Keep boiler room air openings separate and sized for other appliances and ventilation (see Figure 33).
Disconnect power before maintenance
Weil-McLain · All Ultra Series 4 boilers
Electrical shock hazard. All electrical power must be off before maintenance.
- Disconnect all electrical power to the boiler before any maintenance procedure.
Display backlight colours
Weil-McLain · Unity-CI control, EG / PEG Series 7 boilers
The two-line display backlight shows operating state. No backlight means standby. Green means powered on or buttons in use, and it turns off after 20 minutes without button activity. Blue means initialization or a CH call. Purple means a DHW call. Red means an unconfigured control or an active fault.
- Check backlight colour first to identify the operating state.
- On a red fault, use the Advanced Menu to view parameter states while the fault is active.
Display banner colour meanings
Weil-McLain · ECO Tec Series 3 control display
Blue banner means a heating call or a maintenance screen. Red means an error or limit event. The warm weather shut down (WWSD) blocks space heating above the set outdoor temperature but does not block DHW.
- If the banner is red, check the error or limit event on the display before resetting.
- If the banner is blue and the maintenance screen toggles in standby, the maintenance timer has run out. The boiler still operates normally.
- If space heating does not fire on a mild day, check whether WWSD is active and whether the outdoor temperature is above the WWSD setting.
Do not add cold water to a hot boiler
Weil-McLain · Water boilers
Adding cold water to a hot boiler causes thermal shock, which can crack the heat exchanger.
- Do not add cold water to a hot boiler.
Do not adjust or measure gas valve outlet pressure
Weil-McLain · All Ultra Series 4 gas boilers
The gas valve outlet pressure is factory set for natural gas and propane and must not be changed in the field. Throttle screw adjustment is only for qualified technicians with calibrated instruments.
- Do not measure or change gas valve outlet pressure.
- Use the throttle screw adjustment only if combustion is outside range and only with calibrated combustion test instruments.
Do not alter or share concentric vent assembly
Weil-McLain · Concentric termination
Once the rain cap is cemented the assembly cannot be cleaned without replacement. Cutting or altering the assembly can cause toxic flue emissions. Do not connect other appliances to the vent or multiple boilers to a common vent.
- Do not cut or alter the concentric assembly.
- Do not connect any other appliance to the vent pipe.
- Do not connect multiple boilers to a common vent pipe.
- Replace the assembly if blocked air passages cannot be cleared.
Do not override outdoor reset for space heating
Weil-McLain · All Ultra boilers with outdoor reset
Setting the control to DHW mode when the system is meant for space heating may violate Section 303 of the 2007 Energy Act. See page 137 for compliance information and exemptions.
- Keep the outdoor reset active when the system is intended for space heating.
- Check page 137 of the manual before changing DHW mode for a space heating system.
Do not power external devices from 24V transformer
Weil-McLain · All SVF boilers
The 24V transformer in the boiler is only for listed boiler functions.
- Do not use the 24V transformer output to power any external device not listed in the manual.
Do not service the boiler without a maintenance kit
Weil-McLain · ECO Tec series 3 80/110/150/199
Have the correct ECO Tec maintenance kit on hand before accessing or taking apart the boiler. Replace any damaged components and use only parts intended for this boiler.
- Have the model-specific maintenance kit on hand before starting work.
- Replace components that are damaged or that must be removed to access parts.
Do not use closed-type tank with AQUA PLUS
Weil-McLain · Systems with AQUA PLUS water heaters
The automatic air vent on the AQUA PLUS water heater removes air from the system, which waterlogs a closed-type expansion tank.
- Use only a diaphragm or bladder type expansion tank suitable for automatic air vent applications.
Domestic hot water scald and T&P relief valve warning
Weil-McLain · EG / PEG boilers with domestic hot water
Domestic hot water above 130°F can scald. A temperature and pressure (T&P) relief valve is required for protection against excessive temperature and pressure. Automatic mixing valves must follow the valve maker's instructions.
- Hot water above 130°F scalds quickly
- Children, elderly or physically handicapped persons are at higher risk
- Set domestic hot water to 130°F or less, or the lowest practical setting.
- If installing an automatic mixing valve, follow the valve maker's selection and installation instructions.
- Check water temperature immediately after the first heating cycle and after any adjustment.
- Install a T&P relief valve; it is required.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.