Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Wiring and reconnection precautions

Viessmann · Boiler wiring and controls

Replace any original wire only with an exact equivalent. Label all wires before disconnecting them. Each connection can have only one function or accessory assigned.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before removing them.
  3. Reconnect using the exact equivalent wire.
  4. Verify proper operation after servicing.

Wiring caution during service

Viessmann · Vitocrossal 300 CU3A wiring

Label every wire before disconnecting controls, because wiring errors can cause improper and dangerous operation. Replace any original wire only with an exact equivalent. Verify correct operation after servicing. Disconnect power before servicing.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnection.
  3. Replace any original supplied wire only with the exact equivalent.
  4. Verify proper operation after servicing.

Wiring changes and servicing

Viessmann · Vitodens 200-W B2HA wiring

Replacement wires must be exact equivalents. Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Verify proper operation after servicing.
  4. Each connection can have only one function or accessory assigned.

Wiring noise and shielding

Viessmann · Versatronik 585 and 585D wiring

Keep low-voltage communication wiring away from 120/240 VAC conductors to avoid electromagnetic interference. If that cannot be avoided, use stranded twisted-pair shielded cable and ground only one end of the shield.

  1. Route communication wires away from 120/240 VAC conductors where possible.
  2. If they must run close, use stranded twisted-pair shielded wire.
  3. Ground only one end of the shield.

Wiring practice for low voltage and line voltage

Viessmann · Vitotronic 300 GW6B wiring

Keep low voltage and line voltage leads separate. Strip insulation close to the terminal and bundle tightly. Secure cables with cable ties.

  1. Route low voltage leads and line voltage cables separately.
  2. Strip the insulation as close to the terminals as possible.
  3. Bundle the wires tightly to the matching terminals.
  4. Secure the cables with cable ties.

Wiring safety before servicing controls

Viessmann · Vitodens 222-F, B2TB (19, 35, 68, 125)

Disconnect power before working on the boiler. Label every wire before removing it, because wiring errors can cause improper and dangerous operation. Replace any original supplied wire only with an exact equivalent. Verify correct operation after servicing.

  1. Disconnect power to the boiler.
  2. Label all wires before disconnecting them.
  3. Replace damaged original wires only with the exact equivalent.
  4. Reconnect and verify correct operation before leaving the boiler.

Wiring safety during service

Viessmann · Vitodens 200-W B2HA 80 to 100

Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any original wire only with the exact equivalent.
  4. Verify proper operation after servicing.

Wiring service precautions

Viessmann · Boiler wiring and controls

Label all wires before disconnecting. Wrong wiring can cause dangerous operation. Replace any original wire only with an exact equivalent, and verify proper operation after servicing.

  1. Disconnect power before servicing the boiler.
  2. Label every wire before removing it.
  3. Replace damaged wires only with exact equivalents.
  4. Check operation after reconnecting.

Wiring work and verification

Viessmann · Boiler wiring

Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any original wire only with the exact equivalent.
  4. Verify proper operation after servicing.

Without function display

Viessmann · Vitotronic 200-H HK1S/HK3S

Flashes when a button with no assigned function is pressed. Example: the DHW button when no DHW tank is connected.

Work on the boiler only with power and fuel off

Viessmann · All service work

Only a licensed professional heating contractor may install, adjust, service or maintain the boiler. There are no user serviceable parts on the boiler, burner or control.

  1. Turn off main power to the boiler, heating system and all external controls.
  2. Close the main gas or oil supply valve.
  3. Take steps to prevent power being restored during service work.
  4. Verify field-supplied controls such as low water cut-offs, staging controls, pumps, motorized valves, air vents and thermostats.

Working on the boiler: isolate power and fuel

Viessmann · Vitorond 100 VR1 boilers

Before any service, make sure power cannot be applied accidentally to the boiler, heating system or external controls.

  1. Shut off main power to the boiler, the heating system and all external controls.
  2. Close the main fuel supply valve. The manual text says gas supply valve; for this oil-fired boiler, confirm the correct oil shutoff.
  3. Take precautions to prevent accidental power activation during service work.

Working on the equipment

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

Only qualified, licensed personnel may work on the boiler or heating system.

  1. Disconnect main power to the boiler, heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take precautions so power cannot be restored accidentally during service.

Working on the equipment: isolate before service

Viessmann · Vitodens 200-W B2HB, all models

Only a licensed professional heating contractor should install, adjust, service or maintain the boiler. There are no user-serviceable parts. Power and gas must be off before work begins.

  1. Switch off main power to the boiler, the heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take steps so power cannot come back on accidentally during service.

Yearly and two-yearly service

Viessmann · Vitocrossal 300 CA3B

Boiler must be cleaned at least once a year by a qualified heating contractor. The heating system must be serviced by an authorized contractor at least every 2 years.

  1. Clean the boiler at least once a year.
  2. Have the system serviced by an authorized contractor at least every 2 years.
  3. Refer to the installation and service instructions for the full service schedule.

Zone circuit pump connection

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

A maximum of 2 zone circuit pumps can connect directly to the boiler. More pumps need an AM1 extension module. Pump output assignment is done in the set-up wizard.

  1. Connect up to 2 zone circuit pumps directly to the boiler.
  2. For additional pumps, install an AM1 extension module and connect the pumps there.
  3. Assign the pump outputs in the set-up wizard.
  4. Refer to the AM1 Installation Instructions for details.

Zone circuit thermostat connections

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

Each zone circuit takes a dry-contact room thermostat. Up to three zone circuits are shown, and the EA1 module is integrated into the boiler.

  1. Connect the dry-contact room thermostat for zone circuit 1 to the EA1 module.
  2. Connect the dry-contact room thermostat for zone circuit 2 to the EA1 module.
  3. Connect the dry-contact room thermostat for zone circuit 3 to the EA1 module.

Zone control operational screen indications

Viessmann · Vitodens 222-F B2TB 68 and 125 with zone control

What the home screen shows when a zone control circuit is active or configured.

  1. Check which ZC circuit (ZC1, ZC2 or ZC3) is shown, selected with the left or right arrows.
  2. An r on the display means a ZC call is present.
  3. A p symbol means that ZC circuit has an associated pump output.
  4. Read the actual boiler water temperature from the display.
  5. A flame symbol with a percentage shows burner ON and modulation level.
  6. Read the target zone temperature. Fixed Setpoint shows the configured temperature. Weather Compensated shows the target based on slope and shift.
  7. When Weather Compensated is set, the outdoor temperature is also shown.

Zone control operational screen indicators

Viessmann · Vitocrossal 300 CU3A zone control

The zone control screen shows: 1) the ZC circuit selected (left/right arrows to change); 2) an r when a zone call is present; a p when that circuit has a pump output configured; 3) actual boiler water temperature; 4) flame symbol and modulation percentage when the burner is on; 5) target zone temperature (fixed setpoint, or calculated from slope and shift); 6) outdoor temperature when weather compensated control is configured.

  1. Use the left and right arrows to pick the ZC circuit to view.
  2. Look for r for an active zone call and p for a configured zone pump.
  3. Read flame and modulation % when the burner is firing.

Δt control for condensing

Viessmann · Vitocrossal 200 CI2 boilers

Δt control keeps a fixed spread between supply and return. At low load the pump speed is reduced so return temperature stays low. The target spread is interpolated between two points: at 68°F (20°C) supply it uses parameter 2779.0 (factory 9°F / 5 K), and at 194°F (90°C) supply it uses parameter 2779.1 (factory 36°F / 20 K).

Additional heat demand (AHD) behaviour

Weil-McLain · ECO Tec Series 3 priority menus

AHD can be set to 1st, 2nd or Outdoor Temperature. With 1st, the contact closes at once on a call and the boiler starts only if the call is still active when RESPONSE TIME expires and the system is below target minus system-on differential. With 2nd, the boiler starts immediately and the AHD contact closes after RESPONSE TIME. TEMP DEPENDENT = YES requires system supply below target before the AHD contact and 0-10V output act; this needs a valid supply and return sensor pair. The outdoor setpoint option needs a valid outdoor sensor. A master boiler cannot use AHD on a local priority; network AHD must be wired to the master.

Air inlet is not a forced-air intake

Weil-McLain · Multiple boiler and adjacent appliance spacing

The boiler air inlet is part of a direct vent connection. Spacing from adjacent boiler vents is not judged as a forced-air intake.

AL29-4C stainless vent pipe adapter

Weil-McLain · Concentric vent with AL29-4C stainless vent pipe

AL29-4C stainless vent pipe needs the vent pipe maker's PVC adapter when joining to the concentric vent attachment.

  1. Use the vent pipe manufacturer's PVC adapter at the concentric vent attachment.

AL29-4C stainless vent pipe requires a manufacturer adapter

Weil-McLain · AL29-4C vent pipe on Ultra boilers

When using AL29-4C stainless vent pipe, a PVC-to-vent adapter is needed at the boiler vent connection, and also at the termination when using the Weil-McLain plate or the concentric termination.

  1. Use only the adapter made by the vent pipe manufacturer.
  2. Install the adapter at the boiler vent connection.
  3. Install a second adapter at the termination when using the Weil-McLain plate or concentric termination.

Alarm and additional heat demand dry contacts

Weil-McLain · Ultra U-Control dry contacts

The alarm contact on P16 terminals 4 and 5 closes when the boiler enters lockout, for remote alarm notification. The additional heat demand contact on P16 terminals 6 and 7 starts another heat source. Both are low voltage only.

  1. Connect the remote alarm to P16 terminals 4 and 5 if notification is needed.
  2. Connect the next heat source to P16 terminals 6 and 7 if using additional heat demand.

Altitude derate

Weil-McLain · ECO Tec 80/110/150/199 Series 3

From sea level to 2,000 ft the boiler needs no changes and derates itself about 4% per 1,000 ft above sea level. Ratings in the table are for sea level only.

  1. Check the installation altitude.
  2. Use the sea-level ratings only at sea level; above that, expect the automatic derate.

Altitude derate and high altitude settings

Weil-McLain · SVF 1500-3000 Series 1

Above 5,500 ft the control parameters must be changed as the high altitude section of the manual describes. Below that, no change is needed.

  1. Check the site elevation.
  2. Above 5,500 ft, follow the high altitude section and change the listed control parameters.
  3. Record the high altitude setting on the data collection sheet.

Aluminum heat exchanger water chemistry

Weil-McLain · Ultra Series 4 boilers

The Ultra heat exchanger is aluminum. System pH must stay between 7.0 and 8.5 and water chemistry must be checked. Chemical treatment may be needed. Sediment and scale can damage the heat exchanger, and fresh make-up water shortens boiler life.

  1. Flush the system thoroughly before connecting the boiler to remove sediment.
  2. Install a strainer or other sediment removal if needed.
  3. Check water pH and chemistry and treat as needed (see page 35).
  4. Repair leaks at once to stop make-up water from entering.
  5. Use the boiler only in a closed-loop system.
  6. Do not add cold water to a hot boiler.

Antifreeze use in hydronic systems

Weil-McLain · Freeze protection in water boilers

Use only antifreeze made for hydronic systems; inhibited propylene glycol is recommended. Ethylene glycol, automotive or undiluted antifreeze must not be used. A 50% propylene glycol/water solution gives protection to about -30°F. Boiler water content is listed on page 89 and the expansion tank volume must be included.

  1. Calculate antifreeze quantity from total system water content, including the expansion tank.
  2. Follow the antifreeze manufacturer's instructions.
  3. If an automatic fill is used, install a water meter to monitor makeup water because glycol leaks before water does.
  4. If freeze protection or circulator exercising is not used, disable FREEZE PROTECT in the ADVANCED MENU under CIRCULATOR settings.
  5. Install a backflow preventer or disconnect from city supply if local codes require it.

Approved vent and air materials and assembly rules

Weil-McLain · ECO Tec Series 3 vent and air piping materials

Use only materials approved for this boiler. Mixing manufacturers, using the wrong plastics, or insulating plastic vent pipe can cause failure.

  1. Use only the materials in Figure 31 (PVC, PVC-DWV, CPVC, ABS for intake only, polypropylene from Simpson-Duravent or Centrotherm, and AL29-4C stainless from approved makers).
  2. Use cement and primer suited to the piping material.
  3. Do not mix pipe from different manufacturers unless using an adapter made for that purpose.
  4. Use a locking collar on every polypropylene joint.
  5. Do not use cellular core PVC, cellular core CPVC or Radel (polyphenolsulfone) in venting.
  6. Do not cover plastic vent pipe or fittings with thermal insulation.
  7. Use the boiler's 3" 3-in-1 vent adapter for 3" PVC, CPVC, PVC-DWV, Simpson-Duravent AL29-4C, and Simpson-Duravent or Centrotherm polypropylene. The air inlet adapter takes 3" PVC only.
  8. Install a bird screen at every vent and air termination. Weil-McLain sidewall vent caps include the screen.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.