Other: Boiler tips (part 37 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
View message history
Viessmann · Vitodens 100-W B1HE/B1KE
Shows past faults, warnings, notes, status and information messages.
- Call up the home screen and open the menu.
- Select Information, then tap OK.
- Select System information, then tap OK.
- Select Message history, then tap OK.
- Select the message group: fault, warning, note, status or information, then tap OK.
- Select the message and tap OK to view it.
- Hold the exit button for about 4 seconds to leave the menu.
View solar energy yield
Viessmann · Vitotronic 300-K with solar thermal system
The solar energy yield for the past 7 days is shown as a graph. The flashing line marks the current day, which is not finished yet.
- Open the extended menu.
- Select "Solar energy".
Viewing actual temperatures and status
Viessmann · Versatronik 200 system control
Use the Display menu to check live temperatures and status for the DHW, heating circuits and system. A value shows only if its sensor is connected and reading. Otherwise the screen shows "----" or nothing.
- Press the Home button to open the Main Menu.
- Turn the rotary dial until Display is on screen.
- Press the key beside Display to open it.
- Select DHW, Heating Circuit 1 or System to view that circuit's temperatures and status.
- Press Cancel to leave the current screen.
Viewing service contact details
Viessmann · Vitotronic 300-K MW2C
The heating contractor's details can be read on the display if they have been entered.
- From the home screen tap Menu.
- Tap Information.
- Tap Service contact details.
- If no details are entered, tap the white field to open the keyboard. Each text box holds up to 45 characters.
Viewing the service address
Viessmann · Vitocrossal 300 CA3B Dual Fuel boiler
The heating contractor can enter their contact details here. If no details are entered, the field is blank and the keypad can be used to enter them.
- From the home screen, tap Menu.
- Tap Information.
- Tap Service address.
- If no details are shown, tap the white field to open the keypad and enter the contact details.
Vitocontrol-S must be set as fault manager for maintenance messages
Viessmann · Vitocontrol-S VD2/CT3/CM2 control unit
Vitocontrol-S shows maintenance messages from a connected Vitotronic 100 GC1 only when it is encoded as fault manager.
- Check that coding 79 is set to 1 on Vitocontrol-S.
Vitodens 222-F key components
Viessmann · Vitodens 222-F B2TB
Main features of the Vitodens 222-F boiler.
- Stainless steel Inox-Radial heat exchanger.
- Modulating MatriX cylinder gas burner.
- Integral diaphragm expansion tank.
- Digital boiler control unit.
- Integral 3-speed high efficiency circulation pump.
- Stainless steel DHW primary storage tank.
Vitotronic 100 display symbols
Viessmann · Vitotronic 100 GC1B
Symbols do not always show and depend on system version and operating state. Flashing symbols mean a value can be changed. Menu, information and further-adjustment icons appear on the display. Symbol S means emissions test mode, a heating program symbol shows the active program, and symbol 9 means standby with frost protection monitoring. In standby the boiler is available to the cascade control for heat production. If a boiler is not operational, the Vitotronic 100 shows a message on its display. In multi-boiler systems each Vitotronic 100 shows its boiler number on the standard display. Service message: service interval has expired. Fault message: a fault is present. Other symbols show a circulation pump running at a given output and a burner in operation. A D symbol indicates factory settings.
- If the standard display shows a service symbol, the service interval has expired; arrange service.
- If the standard display shows a fault symbol, scan the fault messages and act on them.
Vitotronic 100 keys
Viessmann · Vitotronic 100 GC1B
Function of each key on the Vitotronic 100 programming unit.
- Back key: goes to the previous menu step or cancels a started setting.
- Cursor keys: scroll the menu and set values.
- OK key: confirms the selection or saves the setting.
- Menu key: opens the menu for settings and scanning.
- Question mark key: no function.
Vitotronic 200 control keys
Viessmann · Vitotronic 200 type H01B
The Vitotronic 200 has a back key, cursor keys, an OK key and a menu key. The question mark key has no function.
- Press the back key to return to the previous menu step or cancel a setting that was started.
- Use the cursor keys to scroll through the menu or change values.
- Press OK to confirm a selection or save a setting.
- Press the menu key to open the settings and scanning menu.
- Do not expect the question mark key to do anything.
Wake the cascade control screen
Viessmann · Vitotronic 300-K cascade control programming unit
The touchscreen goes into screensaver mode after a period of no use. Any touch wakes it up.
- Tap anywhere on the screen to wake the screensaver.
- Tap the on-screen buttons to make adjustments or scan information.
Wake the touchscreen and reach the home screen
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0 with Vitotronic 300 GW6C / HI932
The control unit shows a screensaver after a period of no use. Tap the display to wake it. From any menu level, the home button returns you to the home screen. Use the on-screen buttons for all adjustments and scans.
- If the screensaver is active, tap the display anywhere.
- From anywhere in the menu, tap the home button to return to the home screen.
- To open the main menu from the home screen, tap the menu button. From elsewhere in the menu, tap the menu button, then the main menu button.
Wake up display on lag boiler (lead cascade only)
Viessmann · Lead boiler in a cascade
Used from the lead boiler to wake the display of a lag boiler in a cascade.
- Select 'Wake up display'.
- Select and confirm the lag boiler.
Wall mounting the boiler
Viessmann · Vitodens 100-W wall mounting
The wall bracket is supplied for concrete walls. Other materials need anchors rated for 190 lb (86 kg).
- Mark the rawl plug holes on the wall.
- Drill the holes and insert the rawl plugs.
- Fasten the bracket tightly with the supplied screws.
- Hang the boiler and confirm all four bracket tabs are locked in.
- Remove the plastic caps only just before connecting pipes.
Warm-up optimization
Viessmann · Versatronik COMO OT
Automatic advance starts heating earlier, based on weather and room temperature, so the room reaches setpoint at the programmed time. The maximum advance is set separately. The required advance shows for information only.
- Turn warm-up optimization ON.
- Set the maximum time advance.
- Check the required time advance display if needed.
Warn the user about high DHW outlet temperature
Viessmann · DHW tank heating and hygiene function
Raised DHW temperatures at draw-off points can scald. This applies when the DHW target is raised, including during hygiene runs.
- Inform the system user of the scald risk from the higher outlet temperature at draw-off points.
Warranty exclusion for low return temperatures
Viessmann · Vitorond 200 VD2 boilers
Warranty does not cover flue gas condensation corrosion caused by low boiler or return water temperatures.
- Maintain the minimum boiler and return water temperatures listed for the fuel and control mode.
- Use clean fill and make-up water.
Water condition log
Viessmann · Vitocrossal 300 CA3B 2.5 to 6.0
Water condition log on the page records counter reading, fill and make-up water, total water quantity, total hardness, feed water and boiler water pH, and the date.
- Record counter reading, fill and make-up water quantity and total water quantity.
- Record total hardness of the feed water and boiler water.
- Record pH of feed water and boiler water with the date.
Water damage to boiler or controls
Viessmann · Vitotronic 200 and 300-K
Do not use the boiler if any part has been under water. The control system and any gas control that was under water must be replaced by a qualified heating contractor.
- Do not run the boiler if any part has been flooded.
- Have a qualified heating contractor inspect the boiler.
- Replace the control system parts and any gas control that were under water.
Water exposure
Viessmann · Vitocrossal 300 CA3B
A boiler exposed to water must not be run until a qualified contractor has inspected it.
- Do not operate the boiler if any part has been under or exposed to water.
- Have a qualified heating contractor inspect the boiler.
- Replace any control or gas control part that was under or exposed to water.
Water quality
Viessmann · Vitocrossal 300 CA3B
Water quality affects the life of the whole system. Hard water causes deposits on heat exchanger surfaces.
- Avoid hard water (calcium carbonate) conditions.
- Use a water treatment system to protect against corrosion and lime formation.
- If unsure of water quality, have a water analysis done.
Water quality and hard water
Viessmann · Vitocrossal 200 CM2 186 to 620
Water quality affects system life. Water treatment protects against corrosion and lime. Hard water (calcium carbonate) deposits on heat exchanger surfaces and should be avoided. If unsure, get a water analysis.
- Use a water treatment system to prevent corrosion and lime formation.
- Get a water analysis if water quality is in doubt.
Water quality for the heating system
Viessmann · Heating system water
Water quality affects the life of the whole system. Hard water causes scale on heat exchanger surfaces, and corrosion is a risk without treatment.
- Avoid hard water (calcium carbonate) in the heating system.
- If in doubt, have a water analysis done.
- Use a water treatment system to protect against corrosion and lime formation.
Water treatment and fill water
Viessmann · Vitorond 200 VD2A hydronic system
Treat boiler feed water where high mineral content or hardness is known. Warranty does not cover damage from contaminated fill or supplementary feed water.
- Consider water treatment in areas with known high mineral content or hardness.
- Do not operate with contaminated fill or supplementary feed water.
Water-damaged appliance
Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125
Do not use the appliance if any part has been under water. A qualified technician must inspect it and replace the control parts and any gas control that was under water.
- Do not run the appliance after water exposure.
- Call a qualified service technician to inspect the appliance and replace affected control and gas parts.
Weather-compensated mode
Viessmann · Vitotrol 300A
The heating flow temperature follows the outside temperature, so no extra heat is made beyond what the room set point needs.
- The outside temperature is measured by a sensor mounted outside the building and sent to the control unit.
What the remote control can adjust
Viessmann · Vitotrol 300 with Vitotronic control unit
Only the normal room temperature setting is kept on the remote itself. The other adjustments are sent to the Vitotronic control unit and back. Changes to the domestic hot water temperature range may need coding by the heating contractor.
Where settings are made
Viessmann · Vitotronic 200 and 300-K
Each boiler has its own Vitotronic 200 constant temperature control. A higher-level Vitotronic 300-K weather-compensated cascade control regulates these boiler controls. All heating system settings can be changed centrally at the Vitotronic 300-K programming unit, or at remote control units if the system has them.
- Make system-wide changes at the Vitotronic 300-K programming unit.
- Use remote control units for changes if the system has them.
- Use the Vitotronic 200 operating instructions for settings at the boiler control.
Where this control is approved for use
Viessmann · Vitotronic 100 GC1, control part nos. 7134 553 / 7134 554 / 7511361 from serial no. 7143 002
The Vitotronic 100 GC1 is certified only as a component of Viessmann boilers. It covers single-boiler systems and multi-boiler systems with an external building automation system. It does not apply to multi-boiler systems that use the Vitocontrol-S (VD2/CT3/CM2).
Wiring accessory terminals on the DIN rail
Viessmann · DIN rail accessory connections
The accessory terminals are push-in type. Press the orange button before inserting or removing any wire. Solid, stranded, or stranded with ferrule wire can be used; a ferrule helps prevent stranded wire from fraying.
- Press the orange push-in button for the terminal.
- Insert or remove the wire.
- Use a ferrule on stranded wire where possible.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.