Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Use the footer buttons

Viessmann · Vitotronic 300-K cascade control programming unit

The footer buttons go to the home screen, go back one menu level or cancel a started setting, open the help text, open fault or service messages, and scroll through menu options when more are available.

  1. Use the home button to return to the home screen.
  2. Use the back button to go up one menu level or cancel a setting in progress.
  3. Use the help button for help text.
  4. Use the messages button to open fault or service messages.
  5. Use the scroll button to move through extra menu options.

Use two-hand wrench method on boiler and CombiPLUS connections

Viessmann · Boiler and CombiPLUS fittings and piping

Support the connector with one wrench while tightening the fitting or pipe with the second. Failing to support the connections can damage the boiler or the CombiPLUS internal piping.

Using the screen, rotary knob and function keys

Viessmann · Versatronik 200 System Control user interface

The large screen shows four lines: day/date/time, favourites, heat generator or low loss header temperature, and central operating mode. The screen also shows fault indications and a relay test. Menus are moved through with the rotary knob, and a selection is confirmed with a function button. The Home button switches between the information screen and the main menu.

  1. Press Home to switch between the information screen and the main menu.
  2. Turn the rotary knob to move through menus or change a value.
  3. Press the function button beside a line to adjust that value or open its extra displays.
  4. Confirm the selection with the function button marked OK.

UV resistant PP(s) pipe outdoors

Viessmann · PP(s) vent systems

Outside exposed PP(s) exhaust and intake pipe must be UV resistant.

  1. Use UV resistant polypropylene for all exposed exhaust and air intake piping and elbows.
  2. Use the vent manufacturer's supplied material.

Vacation schedule (holiday program)

Viessmann · All heating circuits

Applies to all heating circuits. With Heating and DHW selected, the rooms go to the reduced temperature and DHW heating is off. With Only DHW selected, boiler and DHW tank frost protection is on. The program is only enabled after the departure and return dates are confirmed with OK. Contractor help is needed to change the program.

  1. Open the extended menu and select Heating.
  2. Select Vacation schedule.
  3. Set the departure and return dates and confirm with OK.
  4. To remove it, select Delete schedule and confirm with OK.

Vent clearance to combustibles

Viessmann · Stainless steel and polypropylene venting

Vent clearances to combustibles for stainless steel and polypropylene systems follow the vent manufacturer's requirements.

  1. Check the vent manufacturer's clearance requirements before installing the vent.

Vent pipe adaptor by model size

Viessmann · VR1 22 to 33, 91 to 140, 40 to 63, 161 to 245

A 5 in vent pipe adaptor ships with VR1 22 to 33 and 91 to 140. The adaptor is not supplied with VR1 40 to 63 and 161 to 245.

Vent routing and combustion air seal

Viessmann · Venting for Vitodens 100-W WB1B

The boiler has a factory fitted vent adaptor. Route the vent to the outdoors on the shortest path with a rising slope. Use the separate venting manual for the vent system itself.

  1. Run single-pipe, two-pipe or coaxial venting through the side wall, roof or chimney by the shortest route.
  2. Keep the vent rising at least 3 degrees.
  3. On coaxial installs, remove the plastic centre of the combustion air inlet seal and leave the rubber seal in place.
  4. Follow the Vitodens Venting System Installation Instructions.

Vent termination spacing for multiple boiler installations

Viessmann · Multiple Vitocrossal 300 CA3B Dual Fuel boiler installations

Keep the vent terminations of multiple boilers apart by the minimum distances shown.

  1. For horizontal vent terminations, keep at least 36 in. (915 mm) between them.
  2. For vertical vent terminations, keep at least 4 in. (100 mm) between them.
  3. The page also shows a 6 in. (150 mm) minimum dimension without a label. Check the full venting section before relying on it.

Vent wall penetration and insulation for polypropylene systems

Viessmann · Polypropylene (PP(s)) venting

These rules apply to polypropylene venting only. The wall thickness range and insulation rule are below. The insulation thickness value is garbled in the source, so confirm it in the full manual.

  1. Keep the horizontal vent-air intake wall thickness between 1 in. (25.4 mm) and 30 in. (762 mm).
  2. Seal the vent-air intake system properly.
  3. Insulate polypropylene venting that passes through an unheated space such as an attic, with enough R-value to prevent condensate freezing.
  4. Install the vent termination on the leeward side of the building where possible.
  5. Protect nearby building surfaces from flue products with corrosion-resistant material if needed.

Ventilation and radiator tips

Viessmann · Vitotrol 300A users

Simple habits that help the system keep energy use low.

  1. Open windows fully for a short time while closing the thermostatic valves.
  2. Close roller shutters at dusk, if installed.
  3. Set thermostatic valves correctly.
  4. Do not cover radiators or thermostatic valves.

Venting and combustion air

Viessmann · All Vitodens 200-W B2HB models

Never run the boiler without an installed venting system, because an improper vent can cause carbon monoxide poisoning. The boiler needs adequate combustion and ventilation air and must not be run where the combustion air is contaminated with dust, lint or chemicals.

  1. Confirm a complete venting system is installed before firing the boiler.
  2. Check that combustion air is not contaminated by dust, lint or chemicals.
  3. Check that the mechanical room has adequate combustion and ventilation air.

Venting and common-vent limits

Viessmann · Vitodens 200-W B2HA 19, 28, 35

Do not common-vent the Vitodens 200-W with any other appliance. Side wall coaxial vent installs must include the Viessmann protective screen. Do not exceed the maximum equivalent vent length in the Venting System installation instructions.

  1. Confirm the vent run does not exceed the maximum equivalent length in the Venting System installation instructions.
  2. Confirm no other appliance is connected to the vent.
  3. Confirm the Viessmann protective screen is fitted on a side wall coaxial vent.

Venting and flue checks

Viessmann · Vitocrossal 200 CI2

Blocked venting can cause flue gases to leak into the building.

  1. Check regularly for debris that could block the vent or chimney.
  2. Have any blockage removed by a qualified heating contractor.
  3. Check flue pipes, joints, vent dampers and side wall terminals for moisture or rust.
  4. Never operate the boiler without an installed venting system.

Venting approval and combustion air

Viessmann · Vitorond 200 VD2 boilers

Venting limits and air quality rules apply at installation.

  1. Do not use side wall venting; this boiler is not approved for it.
  2. Do not install the boiler where chlorine, bromine, fluorine or other corrosive chemicals are stored or used.
  3. Keep combustion air free of corrosive chemicals and dust.
  4. Provide combustion and ventilation air at installation per local code and the referenced installation codes.

Venting connection and building protection

Viessmann · Vitodens 100-W WB1B venting

Follow the separate Vitodens venting system installation instructions supplied with the boiler for all venting requirements. Flue products can stain or damage nearby building surfaces, so shield exposed surfaces with corrosion-resistant material such as aluminum sheeting if needed.

  1. Attach and seal any protective material to the building before fitting the vent termination.
  2. Install the vent termination on the leeward side of the building where possible.

Venting in marine or salt-air locations

Viessmann · Vitodens 100-W WB1B in coastal areas

Boilers in damp, salty coastal areas corrode faster. Direct vent (outdoor combustion air) systems are not allowed there, so use room-air-dependent venting.

  1. Do not install direct vent systems in marine environments.
  2. Use a room-air-dependent vent system so the boiler takes combustion air from the room.

Venting length and common venting limits

Viessmann · Vitodens 200-W B2HB

Vent length can go up to 180 ft (55 m). Common venting rules differ by size. B2HB 19-35 and 68-125 may not be common vented with any other appliance. B2HB 45, 57, 160 and 199 may only be common vented with other Vitodens 200-W boilers of the same size and series.

  1. Follow the Installation Instructions for the Vitodens 200-W B2HB Venting System for maximum equivalent length.
  2. For side wall coaxial installs, a Viessmann protective screen must be installed.
  3. Do not common vent B2HB 19-35 or 68-125 with other appliances.
  4. Only common vent B2HB 45, 57, 160 and 199 with the same size and series Vitodens 200-W boilers.

Venting must always be installed

Viessmann · Vitotronic 300-K MW2C boiler system

Never run the boiler without an installed venting system. Improper venting can cause carbon monoxide poisoning.

  1. Confirm the venting system is installed before operation.
  2. Refer to the Installation Instructions for venting and chimney requirements.

Venting near building surfaces

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Flue products from close-by vent terminations can stain or damage some building materials. Protect exposed surfaces with corrosion-resistant material if needed.

  1. Shield or seal exposed building surfaces with corrosion-resistant material such as aluminum sheeting if needed.
  2. Attach and seal the protective material to the building before fitting the vent termination.
  3. Install the vent termination on the leeward side of the building where possible.

Venting options and vent length

Viessmann · Vitocrossal 300 CU3A 26 to 199

Vent length can be up to 198 ft (60 m). Coaxial, double-pipe and single-wall venting are permitted, with the vent system supplied by the installer. Zero clearance to combustibles applies when vented with a listed single-wall special venting system.

  1. Select a venting type from the approved options: sealed combustion coaxial, double-pipe, or single-wall.
  2. Keep the total vent length within the limit given in the venting installation instructions.
  3. Install the Viessmann protective screen on side wall coaxial installations.

Venting restrictions

Viessmann · Vitodens 200-W B2HA 19, 28, 35

Do not common-vent this boiler with any other appliance. Side wall coaxial installs need the Viessmann protective screen and must not exceed the maximum equivalent length in the venting instructions.

  1. Do not common-vent with any other appliance.
  2. Install the Viessmann protective screen on side wall coaxial vents.
  3. Keep the coaxial run within the maximum equivalent length in the Venting System instructions.

Venting: make sure all flue gases exit outdoors

Viessmann · Vitocrossal 300 CU3A venting

Flue gases can contain carbon monoxide. Failing to vent all flue gases safely to the outdoors can cause property damage, serious injury or death. Never run the boiler without an installed venting system.

  1. Verify the venting system is complete and vents all flue gases to the outdoors before commissioning.

Versatronik 200 control overview

Viessmann · Versatronik 200 System Control

Controls up to 8 boilers through CoCo communication modules, a stand-by demand on/off boiler, DHW production, and 2 mixing valves. The screen shows 4 lines, and menus are moved with a rotary dial and confirmed with a function button.

Versatronik 200 menu structure overview

Viessmann · Versatronik 200 System Control, all menu levels

The control menu is split into a User level and an Expert level. The Expert level holds the Configuration and Heat Source Settings branches, plus Heating Circuit 1 and 2, DHW, Solar/MF, Cooling operation and Slab curing. Sub-options listed in the tree include Cascade, Tank, 0-10 I/O, HC Function (Standard* or Const supply), Pool and Return Flow. Pages 80-88 show the tree only, with no values or codes.

Vibration and noise control

Viessmann · Vitorond 200 VD2A installations

Vibration and noise from the boiler and pumps can carry into the building. Measures are needed at the design stage. Attic installations need particular care.

  1. When sizing anti-vibration supports, include the full operating weight of the boiler system.
  2. Install compensators in the boiler flow, return and safety pipes, as close to the boiler as possible.
  3. Insulate braces or hangers against sound and vibration transfer.
  4. Consider silencer hoods, sound-insulated air inlets and room for a flue gas silencer behind the boiler.
  5. Include the silencer's exhaust pressure drop in the vent size calculation.

View 7-day solar energy yield graph

Viessmann · Vitotronic 300-K with solar thermal system

The graph shows solar energy yield for the past 7 days. A flashing line means the current day is not finished yet.

  1. Open the extended menu.
  2. Select "Solar energy".

View fault and message history

Viessmann · Vitodens 100-W B1HE/B1KE

The 10 most recent faults, including remedied ones, and service messages are stored, sorted by date.

  1. Enter the service menu.
  2. Select Message history, then OK.
  3. Select the category: Faults, Service messages, Status, Warnings or Information.
  4. Select the message, then OK.

View help messages

Viessmann · Control unit help

Help text is available for some displays and functions.

  1. Within the menu, select Help if shown.
  2. Confirm with OK.
  3. Exit the screen.

View licences for the programming unit

Viessmann · Control panel

Shows the open source licence for the programming unit.

  1. Go to the home screen.
  2. Open the menu and select 'Information'. Confirm with OK.
  3. Select 'Open source licences'. Confirm with OK.
  4. Hold the exit control for about 4 seconds to leave the menu.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.