Other: Boiler tips (part 33 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Set the holiday departure and return dates
Viessmann · Holiday program
Enter the dates for the holiday program. The return date defaults to the day after departure.
- Open the cover on the programming unit.
- Press the heating circuit selector button until it lights up.
- Press the holiday program button; the 'Holiday program' display appears.
- Press the confirm button; the departure date shows.
- Adjust with up or down until the departure date is correct.
- Confirm; the return date shows. Adjust with up or down until it is correct.
- Confirm; the display returns to the boiler temperature.
- To set the holiday reduced temperature (rw program only), press the temperature button, adjust, and confirm.
- Close the hinged cover.
Shielding and separation of field wiring
Viessmann · Versatronik 502 and 502D field wiring
When extending wire there is a risk of electromagnetic interference. Keep runs away from 120/240 VAC conductors.
- Route low-voltage communication wiring away from 120/240 VAC conductors.
- If the run must be near high-voltage wiring, use stranded twisted-pair shielded cable.
- Ground only one end of the shield.
Show acknowledged faults
Viessmann · Vitodens 200-W B2HA 45, 60
Acknowledged faults are shown as a list in the standard menu.
- Select Fault in the standard menu.
- Review the list of current faults.
Show Viessmann fault codes as hex in a BMS
Viessmann · Niagara AX / KitControl based BMS
The gateway sends fault codes as decimal values. Use the BMS to convert them into hex or text for display.
- Use a numeric bit-and object with a mask to show the value in hexadecimal.
- Use a numeric-to-enum object with the full Viessmann code range to get the text.
- Bind a label on the webpage to the converted slot values.
Showing Viessmann fault codes in hex on the BMS
Viessmann · Niagara AX or similar BMS with KitControl objects
The gateway sends fault codes as decimal numbers. To read them as the hex codes shown on the boiler, mask the value in hex and map the decimal values to the code text in the BMS.
- Convert the decimal fault value to hex using a Numeric Bit And object with a mask input.
- Build an enum range in a Numeric To Enum object listing every Viessmann code.
- Point a bound label on the webpage at the matching slot values.
Showing Viessmann fault codes in hex or as text on the BMS
Viessmann · Versatronik 501 / 501D LON gateway fault display
The gateway sends fault codes as a decimal SNVT_count value, but Viessmann controls show them in hexadecimal. Decode them in the BMS software, for example in Niagara AX.
- Use a mask object (Numeric Bit And in KitControl Util) to show the code in hexadecimal.
- To show the fault text, use a Numeric To Enum conversion (KitControl Conversion) and enter the enum range for all Viessmann error codes.
- Point a Bound Label on the px webpage at the matching slot values to display the text.
Shut down the boiler without frost protection
Viessmann · Vitodens 100-W B1HE/B1KE
In this state, frost protection for the boiler and DHW tank is not active. Pumps and diverter valves may seize if left unpowered. Outside temperatures below 37°F (3°C) need frost protection measures.
- Turn off the ON/OFF switch.
- Close the gas shut-off valve and secure it against unauthorized reopening.
- Protect the system from frost if outside temperatures below 37°F (3°C) are expected. Contact the contractor if needed.
- After a long shutdown, reset the time and date.
Shutting off gas to the appliance
Viessmann · Vitodens 200-W B2HA
Use this procedure to isolate the boiler from gas before service.
- Set the thermostat or control to its lowest setting.
- Turn off all electric power to the appliance if service is to be performed.
- Close the main manual gas shut-off valve.
Side wall vent protective screen
Viessmann · Vitocrossal 300 CU3A side wall venting
Side wall vent installations need the Viessmann protective screen.
- Install the Viessmann protective screen on any side wall vent installation.
Side-wall coaxial vent installation rules
Viessmann · Vitocrossal 300 CU3A side-wall coaxial venting
Do not exceed the maximum equivalent vent length in the Vitocrossal 300 CU3A venting system instructions. Do not common-vent the boiler with any other appliance. A Viessmann protective screen is required on side-wall coaxial vent installations.
- Check the equivalent vent length against the venting system instructions.
- Do not common-vent with any other appliance.
- Install the Viessmann protective screen on side-wall coaxial vents.
Size DHW supply and return piping correctly
Viessmann · DHW storage tank piping
DHW piping between the boiler and a Viessmann DHW tank must be at least 1-1/4 in nominal diameter. Undersized piping can cause short-cycling and poor DHW supply. Non-Viessmann tanks need coil pressure-drop calculations against pump head.
- Use at least 1-1/4 in nominal pipe between boiler DHW connections and the DHW tank connections.
- For non-Viessmann DHW tanks, calculate the tank coil pressure drop against the boiler pump head.
- Confirm enough water flow to the boiler heat exchanger.
Slab curing display
Viessmann · Vitotronic 200-H HK1S/HK3S
If slab curing is coded, this display stays on until the function ends.
Slab curing function (mixing valve circuit only)
Viessmann · Mixing valve heating circuit with underfloor heating
Slab curing runs for 30 days and can use one of four temperature curves selected via coding address F1. When the 30 days end, the mixing valve circuit returns to its normal preset parameters.
- Select the curve with coding F1 before activating slab curing.
- Confirm the mixing valve circuit pump is running and supply follows the selected curve.
- Note the date, as the function stops automatically after 30 days.
Smell of gas
Viessmann · Vitocrossal 300 CA3B
Gas smell is an immediate hazard. Do not start the appliance and do not use switches or phones in the building.
- Do not try to light any appliance.
- Do not touch any electrical switches.
- Do not use any phone in the building.
- Call the gas supplier from a neighbor's phone and follow their instructions.
- If the gas supplier cannot be reached, call the fire department.
Solar energy yield
Viessmann · Vitocrossal 300 CA3B with solar control unit SM1 or Vitosolic
Only applies with a solar control unit type SM1 or a Vitosolic solar control unit. The yield is shown as a diagram. Tap a day of the week to see the figure as a number.
- From the home screen, open Solar energy.
- Tap the required day of the week to show the value as a number.
Solar energy yield display
Viessmann · Solar thermal systems with SM1 and Vitosolic
Only with solar control unit type SM1 and a Vitosolic solar control unit. The yield is shown as a diagram; tap a day to see numbers.
- From the home screen, tap Solar energy.
- Tap the required day of the week to show values in numerical form.
Some settings can be changed at the Vitotrol 200 remote
Viessmann · Vitotronic 200-H HK1M with Vitotrol 200
If the system has a Vitotrol 200 remote control, a few adjustments can also be made there. The control unit itself is used for all settings.
Spring return dampers need no relay
Viessmann · Spring return combustion air dampers
Spring return combustion air dampers do not need the field-supplied relay.
Standard and reduced heating mode
Viessmann · Vitotronic 300-K MW1B
In the Heating and DHW program the operating status switches between standard and reduced heating mode. The change times are set in the time program.
- Set the times in the time program to control when standard and reduced heating mode switch
Standard and reduced heating operating status
Viessmann · Heating and DHW operating program with time program
In the Heating and DHW program, the operating status switches between standard heating mode and reduced heating mode. The switching times come from the time program. Standard mode heats to the standard room temperature during occupied periods. Reduced mode heats to the lower room temperature during absence or night setback.
Standard boiler equipment and separately ordered items
Viessmann · All VR1 sizes
The boiler shell includes insulation for VR1 22 to 33 and 91 to 140. Standard equipment includes a 30 psig pressure relief valve, a drain valve and installation fittings. Burners and controls are purchased separately. The boiler stand must be ordered separately.
Standard display symbols
Viessmann · Vitotrol 300A standard display
Symbols appear depending on system version and operating state: frost protection monitoring, central heating with standard or reduced room temperature, party mode, economy mode, solar circuit pump running (with solar systems), current time, and 2 for service message.
Standard equipment cartons and loose parts
Viessmann · Vitorond 200 VD2A delivery
The boiler ships as cast iron sections on skids with several cartons: supply and return headers, insulation panels and cleaning brushes, the boiler control, and installation fittings with safety header. Turbulators and sealing materials are packed inside the combustion chamber.
- Check the cartons against the packing list before installation.
- Find the turbulators, bagged, inside the combustion chamber.
- If sections ship separately, find the push nipples, high temperature silicone and linseed oil graphite sealant inside the combustion chamber.
Standard equipment in the box
Viessmann · Vitodens 100-W B1HE and B1KE
Standard supply includes the wall-mount boiler and installation fittings, 30 psi pressure relief valve, pressure gauge, two fill/drain valves, mounting hardware, outdoor temperature sensor, and an LPG conversion labelling kit.
Standard heating mode vs reduced heating mode
Viessmann · Heating program, time program
Standard heating mode heats rooms to the standard room temperature for periods when occupied. Reduced heating mode heats to the reduced room temperature for absences or nights. The time program sets when the status changes in the heating-and-DHW operating program.
Standby mode
Viessmann · Vitodens 100-W B1HE/B1KE
In standby the boiler is switched off. Only the frost protection of the boiler and the DHW tank is active. There is no central heating and no DHW heating.
Static and EMI precautions
Viessmann · Versatronik 200 control and sensor wiring
Static-sensitive components can be damaged by poor handling inside the control, so take anti-static measures. Sensor and extension wiring can pick up electromagnetic interference. Use stranded, twisted-pair shielded wire where high-voltage conductors cannot be avoided, and ground only one end of the shield.
- Discharge static before working inside the control.
- Use shielded twisted-pair wire if running near 120/240 VAC.
- Ground only one end of the shield.
Static discharge when opening the control
Viessmann · Vitotronic 200-H control unit
Static discharge to the internal components must never occur when working on an opened control.
- Discharge static before touching internal components of the opened control.
Static sensitive components
Viessmann · Versatronik 511 gateway and boiler controls
Static can damage the control boards. Take all measures to avoid static build-up before working inside the control.
Static sensitive control board
Viessmann · Vitotronic 100 KW10B
The control is sensitive to static discharge. Static can damage internal components whenever the control is opened or handled.
- Follow electro-static discharge precautions before touching the control or its internal parts.
- Avoid static discharge to internal components when the control is open.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.