Other: Boiler tips (part 32 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Screed drying program: behaviour after cancel

Viessmann · Versatronik 200 slab curing

Cancelling or ending the slab curing program returns the controller to the normal operating mode, so heating continues unless the mode is changed.

  1. Cancel or let the program finish.
  2. If no heating is required, set the operating mode to Standby/OFF manually.

Screen status symbols and DEMO mode

Viessmann · Vitocrossal 200 CI2 control unit

Symbols show frost protection, holiday program, and central heating mode with reduced, standard or comfort temperature (weather-compensated or constant). If DEMO shows in the navigation area, there is no central heating, no DHW heating and no frost protection.

  1. If DEMO is shown, do not rely on heating, DHW or frost protection being active.
  2. Check the symbols to confirm the current temperature level and whether the holiday program is on.

Select automatic DHW time program

Viessmann · Domestic hot water time program and DHW re-circulation pump

In automatic mode, domestic hot water heating runs with the central heating time program but starts 30 minutes earlier. The DHW re-circulation pump runs with the DHW time program.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button until 'DHW time program' shows.
  4. Select 'Automatic?' if it is not already shown.
  5. Confirm.

Select boiler size from heat loss

Viessmann · All B2HB models

Pick the boiler model from an accurate building heat loss calculation and check that it suits the connected radiation.

  1. Run an accurate heat loss calculation for the building.
  2. Confirm the chosen model matches the connected radiation.

Sensor and external connection sockets

Viessmann · Vitotronic 200-H control unit

The control has a sockets for the outdoor sensor, supply sensor and external controls. The return sensor is an accessory on the supply sensor socket for underfloor systems.

  1. Connect the outdoor temperature sensor (ATS) to socket X3.
  2. Connect the supply temperature sensor to socket X6. For underfloor systems with the optional return sensor, use X6 for the supply/return sensor.
  3. Connect external controls to socket X5 (aVD). See page 13 for details.

Sensor notes for supply and room sensing

Viessmann · Supply temperature sensor, Vitotrol 300A room sensor

The supply temperature sensor can be used as a contact sensor or an immersion sensor. The room temperature sensor connects at terminals 3 and 4 in the Vitotrol 300A.

Sensor wiring near high voltage

Viessmann · All Vitotronic 300 GW2 sensor and extension wiring

Long sensor runs can pick up electromagnetic interference. Keep sensor wiring away from 120/240 VAC conductors. If that is not possible, use stranded, twisted pair or shielded wire and ground only one end of the shield.

  1. Route sensor wire away from 120/240 VAC conductors.
  2. If a crossing cannot be avoided, use stranded, twisted pair or shielded wire.
  3. Ground only one end of the shield.

Sensors recognized automatically

Viessmann · Application Examples 1, 2 and 3

The flue gas temperature sensor, return water temperature sensor and fault indication module are detected by the control and need no coding. Flue gas temperature is shown and used for limit monitoring.

Separate 120 VAC supply for mixing valve control and accessories

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Accessory power can come directly from the control and is switched by the system on/off switch. The Vitotronic 200-H, HK1B, the mixing valve accessory kit and the Solartrol control need their own 120 VAC supply from a wall receptacle.

  1. Connect accessory power at the control if it is used.
  2. Provide a separate 120 VAC wall supply for the Vitotronic 200-H, HK1B, the mixing valve kit and the Solartrol.
  3. Remember the accessory power follows the system on/off switch.

Serial number for parts orders

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Replacement parts orders need the boiler serial number. Some parts do not work on earlier Vitodens 200-W B2HB versions.

  1. Have the 16-digit serial (bar code label) or the 12-digit ASME/NB serial ready; both are under the front enclosure panel.
  2. Confirm the boiler serial before ordering, because some parts are not reverse compatible.

Service access limits for the end user

Viessmann · Viessmann boilers with Vitotronic 300-K

There are no user-serviceable parts on the boiler, burner or control. Adjustments and service are for a qualified heating contractor only.

  1. Do not perform service or adjustments on system components.
  2. Have the boiler, burners and controls checked at least once per year by the original installer or a competent heating contractor.
  3. Correct defects immediately.

Service address

Viessmann · Vitocrossal 300 CA3B

Shows the heating contractor's service contact details if they have been entered.

  1. From the home screen, open Information.
  2. Select Service contact.
  3. If no details are shown, tap the grey field to open the keypad, then enter the contact details.

Service address entry

Viessmann · Heating system

Heating contractor details can be scanned. Each text box is limited to 45 characters. If no details are entered, the gray fields are blank.

  1. From the home screen, tap Information.
  2. Tap Service contact details.
  3. Tap a gray field to open the keyboard and enter details.

Service and maintenance responsibility

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

There are no user-serviceable parts. Service must be done by a qualified heating contractor, and annual service is required.

  1. Do not let the end user perform service on boiler, burner or control components.
  2. Follow the Service Schedule in the manual (page 41).
  3. Indirect-fired DHW storage tanks must be serviced within two years of installation and regularly after that.
  4. Clean soot build-up from the heat exchanger, since it raises flue gas temperature and reduces efficiency.

Service due indication

Viessmann · Vitotronic 200

When service is due, a service symbol flashes on the display with the burner hours run (for example 05500 h). The heating contractor schedules the maintenance.

  1. Note the service indication and notify the heating contractor.

Service equipment needed

Viessmann · Vitocrossal 200 CI2

Basic tools, cleaning supplies and calibrated test equipment for servicing the boiler.

  1. Bring screwdrivers, pipe wrenches, open-ended wrenches, hex keys and a flashlight.
  2. Bring pipe sealant and approved leak detection fluid for natural gas and propane.
  3. Bring a plastic hand brush, cleaning brush, vacuum and clean rags.
  4. Bring a calibrated flue gas analyzer for % CO2 or O2, a multimeter, a gas pressure gauge (0-28 in. w.c.) and a CO meter (0-400 ppm).
  5. Bring a stack thermometer (0 to 250°F) and a way to calculate efficiency.

Service interval

Viessmann · Vitotronic 300-K MW1B / Vitotronic 100 GC1B

The heating system must be serviced by an authorised contractor at least every 2 years.

  1. Arrange an inspection and maintenance contract with the heating contractor

Service interval and annual cleaning

Viessmann · Vitocrossal 300 CA3B

The boiler needs a qualified service at least every 2 years, and the manual calls for the boiler to be cleaned at least once a year. Dirty heat exchangers raise flue gas temperature and reduce efficiency.

  1. Book service with a qualified heating contractor at least every 2 years.
  2. Have the boiler cleaned at least once a year.
  3. Check the service schedule in the installation and service instructions.

Service interval and boiler cleaning

Viessmann · Vitodens 200-W B2HA

Have the heating system serviced by an authorized contractor at least every 2 years. Boilers should be cleaned annually, because contamination raises flue gas temperature and energy losses. Damaged connecting cables must be replaced with Viessmann cables only.

  1. Arrange an inspection and maintenance contract with the local heating contractor.
  2. Clean the boiler annually.
  3. Replace damaged connecting cables with Viessmann cables.

Service interval reminders

Viessmann · All CM2 models

Regular service keeps efficiency up and flue temperatures down.

  1. Have the heating system cleaned and serviced on a regular basis by a qualified heating contractor.
  2. Service indirect-fired domestic hot water storage tanks within two years of installation and regularly after that.
  3. Keep the boiler and boiler room clean and free of combustible materials and flammable liquids.

Service LED shows communication activity, not BMS traffic

Viessmann · Versatronik 581 gateway, all supported boiler controls

The gateway's service LED blinks with the data exchanged between the gateway and the boilers. It does not reflect communication with the BMS. A single boiler blinks slowly while reading boiler data and faster while reading cascade data. A multi-boiler system blinks at a more uniform rate.

Service lockout before working on the control

Viessmann · Versatronik 10.WB1 service

The control has more than one live circuit. Power to the control and to the damper or blower must be off before any servicing. The control has no user-serviceable parts.

  1. Turn off power to the control.
  2. Turn off power to the damper or blower.
  3. Verify all circuits are de-energised before touching terminals.
  4. Leave repairs of the control to qualified service personnel.

Service menu overview (single boiler)

Viessmann · Vitocrossal 200 CI2 service menu

Top level menus: Diagnosis (General, Burner, Heating circuits 1 to 4, DHW, Communication module, Heating zones 1 to 4, Actuator test, System configuration, Message history); Service functions (Reset service, Filling, Air vent valve, System information, Connectivity information, Test Mode, Emissions Test Mode, High Limit Safety Cut-out Test); Change passwords; Commissioning; Appliances detected; Exit service; Access point on/off.

Service message if service is postponed

Viessmann · Vitodens 100-W B1HE/B1KE

If the service cannot be done on the due date, the service message comes back the following Monday.

Service only by licensed heating contractor, power and fuel isolation

Viessmann · Vitorond 100 oil-fired boiler

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor. There are no user serviceable parts on the boiler, burner or control.

  1. Disconnect main power to the boiler, heating system and all external controls before working.
  2. Close the main fuel supply valve. The manual text says gas supply valve, but this is an oil-fired boiler.
  3. Take precautions to prevent accidental power activation during service work.
  4. Verify field supplied controls such as low water cut-offs, pumps, motorized valves, air vents and thermostats.

Service required code 0f

Viessmann · Vitocrossal 300 CA3B Dual Fuel

Code 0f is shown only in the fault history. It means service is due.

  1. Service the boiler.
  2. After servicing, set code 24:0.

Service restricted to qualified technicians

Viessmann · Vitocrossal 300 CU3A, all models

There are no user-serviceable parts on the boiler, burner or control. Adjustments, service and installation of replacement components must be done by a qualified or licensed heating contractor.

  1. Do not allow the end user to adjust or service boiler, burner or controls.
  2. Use only components tested with this heating system.

Service restriction

Viessmann · Vitorond 200 VD2A, all sizes

Installation, adjustment, service and maintenance must be done by a licensed heating contractor. There are no user-serviceable parts on the boiler, burner or control.

  1. Turn off main power and close the main fuel supply valve before any service work.
  2. Use only original Viessmann or Viessmann-approved replacement parts.

Set a time program for a heating circuit

Viessmann · Central heating and DHW time programs

Each time program allows up to 4 time phases per day. Outside the phases the system drops to the reduced level. DHW is not heated between phases, and DHW tank frost protection stays active. Allow time for the DHW tank to reach temperature before the phase starts.

  1. Select the heating circuit in the menu bar.
  2. Open the time program and select the day.
  3. Set Start and End for time phase 1 and choose the temperature level (Standard or Comfort).
  4. Add time phase 2 if needed, set Start and End, and choose the level.
  5. Confirm and exit the time program.

Set an individual DHW time program

Viessmann · Domestic hot water time program and DHW re-circulation pump

Use this instead of automatic mode when DHW timing must be set separately. The same steps apply to the DHW re-circulation pump.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button until 'DHW time program' shows.
  4. Select 'Individual?' if it is not already shown.
  5. Confirm.
  6. Choose '1-7' for identical days, or a weekday for individual days, then confirm.
  7. Set DHW phase 1 ON time, confirm, set phase 1 OFF time, confirm.
  8. Repeat for DHW phases 2 to 4.
  9. Close the hinged cover.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.