Other: Boiler tips (part 31 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Routing connecting cables

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

Keep connecting cables away from hot components, since heat will damage them. Check that the cable temperature ratings are not exceeded where the cables are routed and secured on site. Low voltage, 120V and external accessory cables connect to the main PCB and the communication module.

  1. Route cables away from hot parts of the boiler.
  2. Check that the cable temperature limits are not exceeded.
  3. For larger cross-sections (up to 9/16 in. / 14 mm), remove the existing cable grommet.
  4. Secure the cable with the cable grommet fitted into the lower casing section (orange).

Routing external cables near hot parts

Viessmann · Vitocrossal 300 CU3A 26 to 199

Cables fail if they touch hot boiler components. Keep power and pump cables within their rated temperature limits.

  1. Route cables away from hot components.
  2. Check that the cable's maximum permitted temperature is not exceeded where it is secured on site.

Sacrificial anode check

Viessmann · Vitocell 100

For Vitocell 100 the sacrificial anode function should be checked annually. This can be done without interrupting system operation.

  1. Have the heating contractor check the ground current with an anode tester

Safe operating requirements

Viessmann · All B2HA models

Never run the boiler without an installed venting system, and never run it with the front cover off. Do not run it in areas with contaminated combustion air.

  1. Confirm the venting system is installed before firing.
  2. Keep the front cover in place during operation.
  3. Check that combustion air is free of dust, lint and chemicals.

Safety before wiring the Versatronik 10.WB1

Viessmann · Versatronik 10.WB1 with Vitodens 100-W WB1A and WB1B

Disconnect power before any work. The pump output from the Vitodens boiler to the Versatronik must not be live. Check all wiring before applying power, or the pump module may fail early. Static sensitive parts can be damaged by handling, so take static precautions.

  1. Disconnect the boiler and the Versatronik from 120VAC before any work.
  2. Check that the boiler pump output to the Versatronik is not live.
  3. Check all wiring connections before applying power.
  4. Use static precautions when working inside the control.

Safety relief valve discharge piping

Viessmann · Vitotron 100 VLN2 relief valve

The 30 psi ASME relief valve must discharge through copper piping to a safe location near the floor.

  1. Install copper piping from the relief valve to within 6 in. of the floor or a floor drain.
  2. Do not install any barrier fitting or valve on the outlet of the safety valve.

Safety rules during service

Viessmann · VR1 40 to 63, 161 to 245

Key warnings for anyone working on the boiler.

  1. Do not use gasoline, crankcase drainings or any oil containing gasoline.
  2. Never adjust the burner by eye.
  3. Do not start the burner unless the combustion chamber door is secured in place.
  4. Do not attempt to start the burner when excess oil has built up, the unit is full of vapor, or the chamber is very hot.
  5. Never fire the boiler without water.
  6. Do not tamper with the unit or controls.
  7. Keep the manual fuel supply valve shut off when the burner is down for a long time.
  8. Never burn garbage or paper in the unit or leave combustible material near it.
  9. Do not leave tools inside the combustion chamber.
  10. Read the fiberglass and ceramic fiber warning on page 3 before handling insulation, and use proper respirator and clothing.

Safety valve (DHW tank) check

Viessmann · DHW tank safety valve

The DHW tank safety valve can become contaminated at the seat. Water may drip from the outlet during heat-up, which is normal. The outlet must stay open to the atmosphere.

  1. Check the function of the safety valve every six months by venting it (see valve manufacturer's instructions).
  2. Do not close off the safety valve outlet.

Safety valve and drinking water filter on DHW supply

Viessmann · Viessmann DHW tank installations

The safety valve is installed by the heating contractor in the cold water pipe. It opens automatically to prevent excess pressure in the DHW tank. A drinking water filter removes solids from the water and is installed in the cold water pipe upstream of the DHW tank or instantaneous water heater.

  1. Verify the safety valve is installed in the cold water pipe.
  2. Verify the drinking water filter is upstream of the DHW tank or instantaneous water heater.

Safety valve and drinking water filter on the cold water supply

Viessmann · DHW tank cold water connection

The contractor installs the DHW safety valve in the cold water pipe. It opens automatically to limit excess pressure in the DHW tank. A drinking water filter, which removes solids, goes in the cold water pipe upstream of the DHW tank or instantaneous water heater.

  1. Install the safety valve in the cold water pipe.
  2. Install the drinking water filter in the cold water pipe upstream of the DHW tank or instantaneous heater.

Safety valve on DHW tank

Viessmann · Vitodens 200-W B2HA domestic hot water tank

The safety valve is installed by the heating contractor in the cold water pipe. It opens automatically to prevent excess pressure in the DHW tank.

Scald protection on DHW piping

Viessmann · Vitodens 100-W B1HE/B1KE DHW outlet

DHW from gas condensing combi boilers can exceed 140°F (60°C).

  1. Install scald protection on site in the DHW pipe.

Scald risk from raised DHW temperature

Viessmann · Vitodens 100-W B1HE/B1KE

Raised DHW target temperatures increase the outlet temperature at draw-off points.

  1. Tell the system user about the scald risk from the higher outlet temperature at draw-off points.
  2. Provide on-site scald protection if needed.

Scald warning for instantaneous DHW

Viessmann · Vitodens 100-W B1KE Combi series

Hot water can cause serious injury. The B1KE with instantaneous DHW has a scalding label on the side of the boiler. Do not touch hot water.

  1. Warn occupants about hot water at the taps.
  2. Keep the scalding label on the boiler visible.

Scan current temperatures and operating data (Vitotronic 300-K)

Viessmann · Vitotronic 300-K

The 300-K groups its scan data into General, Heating circuit 1, 2 and 3, DHW, Solar and Reset data. Named heating circuits show their custom name in the scan list.

  1. Open the extended menu.
  2. Select "Information".
  3. Select the group you need.
  4. Select the required scan.

Scan list for readings

Viessmann · Vitotrol 300A

The scan list shows readings from the boiler and circuits. Not all scans are present on every system, depending on the equipment level.

  1. General: outdoor temperature, boiler temperature, common flow temperature, flue gas temperature, burner hours run (stage 1 and 2), time, date, subscriber number.
  2. Fuel consumption: oil boilers only.
  3. Solid fuel boilers only: idle state, control mode, burnout phase, ember retention, cleaning, buffer cylinder top and bottom.
  4. Heating circuits 1 to 3: heating program, operating status, time program, set and actual room temperature, circuit pump, flow and return temperature, holiday program.
  5. Solar: collector temperature, solar DHW, solar circuit pump and its speed, solar energy, heat suppression.
  6. DHW: DHW time programs HC 1 to 3, recirculation time programs, actual DHW temperature, DHW tank primary pump, DHW circulation pump.

Scan points available under the Information menu

Viessmann · Vitotronic 300-K, type MW2C control, Information menu

The Information menu lists scan points grouped by area: general boiler data, heating circuits 1 to 3, solar, and DHW. Which scans show depends on the installed equipment level, so some listed points will not appear on every system. Some points can be expanded for more detail. Groups include outdoor temperature, boiler sequence and temperatures, sensor and output readings, feed pump, central fault message, heating program and operating status, room and comfort targets, slope and shift, heating and mixer pumps, solar collector and pump data, DHW temperatures and DHW pump status.

Scan points under the Information menu (general and heating circuits)

Viessmann · Vitotronic 300-K MW2C, Information menu

The Information menu lets you scan live values. Which scans appear depends on the installed equipment level. Items marked with an icon in the manual have a detailed view. General scans include outdoor temperature, boiler sequence, boiler temperature, sensors 17 A/B and 9, outputs 20, 29 and 52, feed pump, central fault message, participant number, integral, external input EA1, 0-10 V external hook-up, time and date. Heating circuit 1, 2 and 3 scans include heating program, operating status, time program, room temperature and targets, set external room temperature, comfort and reduced targets, slope, shift, heating circuit pump, mixer, supply temperature and holiday program.

Scan points under the Information menu (solar and DHW)

Viessmann · Vitotronic 300-K MW2C, Information menu, solar and DHW

Solar scans include solar energy history, collector temperature, solar DHW, solar circuit pump run hours and ON/OFF state or pump speed, solar energy, heating suppression of DHW, SM1 output 22 state and run hours, sensors 7 and 10, and heating suppression. DHW scans include DHW time program, DHW circulation time program, DHW temperature, or top and bottom DHW temperatures when two tank sensors are fitted, DHW circulation pump and tank primary pump.

Scan solar energy yield

Viessmann · Vitocrossal 300 CA3B with solar control unit SM1 or Vitosolic

Only works with a SM1 solar control unit, or with a Vitosolic solar control unit. Yield is shown as a diagram. Tap a day of the week to show the figure as a number. The solar circuit pump run hours are in the extended Information menu under the Solar group.

  1. From the home screen, open Menu, then Solar energy.
  2. Tap the required day of the week for a numerical value.
  3. For solar circuit pump run hours, open Menu, Information, then the Solar group.

Scan the preset space heating time phases

Viessmann · Vitotronic 200-H space heating time program

Shows the factory time phases on the time slot graphic without changing them.

  1. Open the hinged cover on the programming unit.
  2. Press ur and the second button at the same time; the preset time phases appear on the time slot graphic.
  3. Close the hinged cover.

Scanned values list

Viessmann · Vitotronic 300 GW2

The temperature scan lists the values below. Some only appear if the matching sensor or remote control is connected.

  1. Damped outdoor temperature (can be reset to current by pressing D).
  2. Current outdoor temperature.
  3. Output reduction %.
  4. Desired and current boiler temperature.
  5. Sensor 17A and 17B current values.
  6. Max. and current flue gas temperature (max. can be reset by pressing D).
  7. Desired and current DHW temperature, plus DHW 1 and DHW 2 if two sensors are fitted.
  8. Desired and current supply temperature.
  9. Desired and current room temperature.
  10. Boiler coding card and scans 1 to 7.

Scanning boiler information and temperatures

Viessmann · Vitocrossal 300 CA3B Dual Fuel boiler, all listed heating circuits and DHW

The main menu groups scan data such as General, Combustion controller, Heating circuits 1 to 3, DHW, Solar energy, Reset data, Opening source licenses and Service address. Available items depend on the equipment connected and the settings made. Items include outdoor, boiler and flue gas temperatures, burner starts and hours, boiler sequence, sensors, heating program, room temperatures, mixing valve, DHW temperatures and pump status.

  1. From the home screen, tap Menu.
  2. Tap Information.
  3. Select the group you need and read the value.
  4. For solar yield values, tap the respective day of the week to show a numerical value.

Scanning heating system information

Viessmann · Vitotronic 300-K MW2C

Live temperatures and operating states are grouped under the Information menu.

  1. From the home screen tap Menu.
  2. Tap Information.
  3. Select the group: General, Burner, Heating circuit 1, 2 or 3, DHW, Solar energy, Reset data or Service address.
  4. Heating circuit names show here if they have been set.

Scanning information

Viessmann · Vitocrossal 300 CA3B

Shows current temperatures and operating conditions. The menu groups depend on connected components and settings.

  1. From the home screen, open Information.
  2. Choose a group: General, Combustion controller, Heating circuit 1, 2 or 3, DHW, Solar energy, Reset data, Opening source licenses or Service contact.

Scanning information groups

Viessmann · Vitotrol 300A remote control

Current temperatures and operating conditions can be scanned. Groups are General, Heating circuit 1, 2 and 3, DHW, Solar and Reset data.

  1. Open the extended menu.
  2. Select Information.
  3. Select the category, then the required scan.
  4. To show a value on the standard display, press OK on items marked Adopt with OK.

Scanning options available under Information

Viessmann · Vitotronic 300-K MW2C

Subject to equipment fitted, not all scans are available. Some items have further detail. Groups are General, Heating circuit 1, 2 and 3, Solar, and DHW.

  1. General: outdoor temp, boiler sequence, boiler temperature, sensors 17 A and 17 B, common supply or demand temp, sensor 9, outputs 20, 29 and 52, feed pump, central fault message, participant number, integral, input ext. EA1, external hook-up 0 to 10 V, time, date.
  2. Heating circuits 1 to 3: heating program (slab curing, external hook-up, holiday, external program, comfort mode, economy mode, heating and DHW, DHW only, standby), operating status (standard heating, reduced, standby), time program, room temperature, room and reduced room targets, external room temp, comfort target, slope, shift, heating circuit pump, mixer, supply temperature, holiday program.
  3. Solar: solar energy history, collector temp, solar DHW, solar circuit pump hours and on/off, solar energy, solar pump speed, heating suppression DHW and heating, SM1 output 22 on/off and hours, sensors 7 and 10.
  4. DHW: DHW time program, DHW circulation time program, DHW temperature or top and bottom temperatures with two sensors, DHW circulation pump, tank primary pump.

Scanning solar energy yield (SM1 with Vitosolic only)

Viessmann · Vitotronic 300-K with SM1 solar control and Vitosolic

Solar yield is shown as a diagram. Only applies with solar control unit SM1 and a Vitosolic.

  1. From the home screen tap Menu.
  2. Tap Solar energy.
  3. Tap a day of the week to show the values as numbers.
  4. For pump hours and other solar scans use the extended menu under Information, Solar group.

Scanning system information

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Current temperatures and operating conditions are shown in grouped menus, depending on the components connected.

  1. Go to Menu > Information.
  2. Select the group: General, Combustion controller, Heating circuit 1-3, DHW, Solar energy, Reset data, Opening source licenses or Service address.
  3. Solar yield requires a SM1 solar control unit with Vitosolic.

Scans 2 to 7 contents

Viessmann · Vitotronic 300 GW2

Scans 2 to 7 show software versions, plug-in adaptors, extension kits, remote control modes, LON data and the equipment identification code. Scan 4 is not assigned. Scans 5 and 6 need the LON module.

  1. Scan 2: software versions of plug-in adaptor, programming unit, control unit and extension kits for M2 and M3.
  2. Scan 3: software versions and operating modes of remote controls for A1, M2 and M3.
  3. Scan 5: Viessmann participant number, node address and subnet/system number (LON).
  4. Scan 6: communication coprocessor and Neuron chip software, LON participant count, SNVT configuration (LON).
  5. Scan 7: equipment identification code.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.