Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Replace the boiler water temperature sensor (3A / 3B)

Viessmann · Boiler water temperature sensors 3A (NTC 10k) and 3B (NTC 20k)

Each boiler section has its own boiler water temperature sensor in a sensor well. Replace the sensor for the affected section.

  1. Remove the spring clip from the sensor well and set it aside.
  2. Pull the boiler water temperature sensor out of the sensor well.
  3. Disconnect sensor cable plugs 3A / 3B.
  4. Connect the new sensor to plugs 3A / 3B and install it in the sensor well.
  5. Reinstall the spring clip.

Replace the burner control unit

Viessmann · Burner control unit

Remove the display and programming unit and all cables before swapping the burner control unit. The coding card moves to the new unit.

  1. Disconnect the KM-BUS connector avG.
  2. Undo the 2 mounting screws on the display and programming unit (torque 1 Nm / 9 lb.in) and lift it off.
  3. Unplug the burner control unit connecting cable and remove the display unit.
  4. Unplug all connecting cables from the burner control unit.
  5. Pull the coding card from the burner control unit.
  6. Undo the 4 mounting screws and remove the burner control unit.
  7. Install the new unit in reverse order.

Replace the fan and Venturi assembly

Viessmann · Fan and Venturi pipe

The Venturi pipe carries the gas valve. Fit the fan gasket in its correct position.

  1. Disconnect both fan connectors.
  2. Remove the 6 Venturi pipe nuts and remove the Venturi pipe with the gas valve attached. Tighten to 6 Nm (4.5 lb.ft) on reassembly.
  3. Undo the hex nuts on the 4 studs.
  4. Remove the fan and note how the gasket sits.
  5. Install the new fan in reverse order and fit the gasket in the correct position.

Replace the gas valve

Viessmann · Gas valve

Check the gas connections for tightness after reassembly. Leak detection spray must not contact electrical contacts. The gas valve mounts horizontally, rotated 90°. The orifice plate must be oriented with its chamfer facing the gas valve.

  1. Disconnect the electrical connectors from the gas valve and both gas pressure switches.
  2. Disconnect the pressure compensation line from the gas valve.
  3. Remove the gas inlet flange screws and remove the flange.
  4. Remove the nuts on the outlet flange and remove the gas valve.
  5. Fit new studs to the new gas valve outlet flange.
  6. Check the orientation of the gas valve and orifice plate.
  7. Replace the inlet and outlet gaskets.
  8. Secure the gas valve on the flange without stress and tighten the screws to 1.5 Nm (13 lb.in).
  9. Reconnect the valve and gas pressure switch connectors and the pressure compensation tubing.
  10. Do not swap the connecting cables of GDW1 and GDW2.
  11. Check the gas connections for tightness.

Replace the ignition unit and ignition cables

Viessmann · Ignition unit and ignition cables

Ignition unit mounting screws are torqued to 1.5 Nm (13 lb.in).

  1. Unplug the connecting cable from the ignition unit.
  2. Pull the ignition cables from the ignition unit.
  3. Undo the ignition unit mounting screws and remove the unit.
  4. Install the new ignition unit in reverse order and torque the screws to 1.5 Nm (13 lb.in).
  5. For ignition cables, pull them from the unit and from the ignition electrodes, then fit the new cables in reverse order.

Replacement parts and electrical isolation before work

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

Only Viessmann recommended parts are allowed. Isolate power and gas before any service work.

  1. Use only original Viessmann recommended components when replacing defective parts.
  2. Turn off main power to the boiler, the heating system and all external controls.
  3. Close the main gas supply valve.
  4. Prevent accidental power-up during service work.
  5. Check the field supplied controls such as low water cut-offs, pumps, motorized valves, air vents and thermostats.

Replacement parts for combustion chamber door

Viessmann · All VR1 models

Commonly needed items for combustion chamber door service.

  1. Use rope sealant for the combustion chamber door seal.
  2. Use refractory for the combustion chamber door.

Replacing damaged cables or lines

Viessmann · Vitocrossal 300 CA3B

Damaged connecting cables or lines on the appliance or on externally installed accessories must be replaced.

  1. Use only Viessmann cables or lines as replacements.
  2. Have a qualified contractor make the replacement.

Required test equipment

Viessmann · Vitocrossal 300 CA3B Dual Fuel

Calibrated equipment is required for combustion and gas checks on this boiler.

  1. Use a flue gas analyzer to measure % CO2 or O2.
  2. Use a multimeter for 0-120 VAC, 0-25 A AC and 0-100 microamps DC.
  3. Use a gas pressure gauge covering 0 to 28 in. w.c. (a Magnehelic 0-10 psig gauge may also be used).
  4. Use a CO meter covering 0 to 400 ppm.
  5. Use a stack thermometer covering 0°F to 250°F.
  6. Have a leak detection fluid approved for natural gas and propane.

Required test tools

Viessmann · Vitodens 200-W B2HA 45, 60

Calibrated equipment is needed for service work on this boiler.

  1. Use a multimeter for 0-230V AC, 0-12A AC and 0-100 mA DC.
  2. Use a flue gas analyzer to measure CO2 or O2.
  3. Use a manometer for gas pressure, 0 to 11 in. w.c. (accurate) and up to 28 in. w.c., or a Magnehelic manometer.
  4. Use a stack thermometer, 0 to 500°F (0 to 260°C).
  5. Use a CO meter, 0 to 400 ppm.
  6. Use a leak detection fluid approved for natural gas and LP, and pipe joint sealant.

Required tools and supplies for service

Viessmann · VR1 40 to 63, 161 to 245

Equipment to have on hand for the service procedure.

  1. Calibrated flue gas analyzer.
  2. Hand brush, rags and vacuum cleaner.
  3. Rope sealant and refractory for the combustion chamber door, if replacement is needed.

Required tools for service

Viessmann · Vitorond 100 VR1 service

Use only calibrated equipment.

  1. Use a calibrated flue gas analyzer.
  2. Have a hand brush, rags and a vacuum cleaner ready.
  3. Keep rope sealant and refractory for the combustion chamber door on hand if replacement is needed.

Resetting data counters

Viessmann · Vitotrol 300A remote control

Burner hours, fuel consumption (if set by the heating contractor) and solar yield or solar pump hours can be reset individually or together with All details.

  1. Open the extended menu.
  2. Select Information, then Reset data.
  3. Select the item, or All details, and reset.

Respond to a fault display (Vitotronic 300-K)

Viessmann · Vitotronic 300-K

A fault turns the red fault display on and it flashes. Fault appears on the display and flashes. Press OK to show the fault code. If a central fault message facility is connected, it starts. Some faults also show a short text.

  1. Press OK to show the fault code.
  2. Look up the code in the fault codes table.
  3. Follow the on-screen instructions to acknowledge the fault.
  4. Check the faulty component as listed in the fault code table.

Return to home screen and standby

Viessmann · Vitodens 100-W B1HE and B1KE control unit

The home screen is the start point for most navigation. The display backlight turns off after about 2 minutes without input.

  1. If the display is in standby, tap any button to wake it.
  2. From anywhere in the menu, tap Back repeatedly until the home screen appears.

Reverse mixing valve motor rotation

Viessmann · Mixing valve motor 7133 390

The motor rotation direction is set by how plug A is fitted. Reverse it when the installation example requires the opposite direction.

  1. Remove the motor cover.
  2. Remove plug A.
  3. Reinsert plug A turned 180°.
  4. Check that the mixing valve opens and closes correctly with the relay test.

Reverse the mixing valve motor rotation direction

Viessmann · Mixing valve motor

To change the direction of rotation, the plug orientation is reversed.

  1. Remove the cover of the mixing valve motor.
  2. Remove the 3-pole plug A and reinsert it turned by 180°.

Roof vent height and chimney routing

Viessmann · Special vent systems with positive vent pressure

Special vent with positive pressure has height and routing limits when passing through a roof.

  1. Extend the vent at least 18 in above the highest roof penetration point and any obstruction within 18 in horizontal distance.
  2. Do not route the special vent into, through or within another vent or existing chimney.
  3. Use a masonry chimney flue only if no other appliance vents into that flue.

Room air dependent versus direct vent combustion air

Viessmann · Boiler combustion air supply

In room air dependent operation, combustion air comes from the room where the boiler is installed. In direct vent operation, combustion air is drawn from outside the building.

Room air dependent vs direct vent combustion air

Viessmann · Boiler combustion air supply

Room air dependent operation draws combustion air from the boiler room. Direct vent operation draws combustion air from outside the building.

Room air vs direct vent combustion air

Viessmann · Vitodens 200-W B2HA venting configuration

Room air dependent operation draws combustion air from the boiler room. Direct vent operation draws combustion air from outside the building.

Room feedback and system type

Viessmann · Versatronik COMO OT room feedback setting

Room temperature feedback can be turned on to improve comfort, and its influence factor changes how the boiler responds. On low-mass emitters like baseboard or panel radiators, and on high-mass radiant floors, feedback may not give the expected result because of how quickly each system responds.

Room influence on supply temperature (worked example)

Viessmann · Heating circuits with room temperature hook-up

The supply temperature rise from room temperature hook-up is: (target room temp - actual room temp) x (1 + slope) x room influence factor / 4. Example from the manual: target 20.0°C, actual 18.0°C, slope 1.4, factor 8 (factory) gives a rise of 9.6 K.

  1. Use the room influence factor parameter for the heating circuit: 933.7, 934.7, 935.7 or 936.7.

Room temperature-dependent vs weather-compensated control

Viessmann · Heating control modes

Room temperature-dependent mode controls supply temperature from a room sensor fitted in the room, independent of outdoor temperature. Weather-compensated mode controls supply temperature from an outdoor sensor fitted on the building exterior.

Rotary damper must be fully open

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

An incompletely opened rotary damper can cause malfunctions or point to incorrect servomotor adjustment.

  1. Confirm the rotary damper is fully open with the burner off and during operation.
  2. If it is not, adjust it with the articulated rod and check the servomotor settings.

Route and secure field wiring

Viessmann · Vitodens 200-W B2HA 80-100, 285-352

Keep connecting cables away from hot components and do not exceed their maximum temperature rating. Use the cable grommet for power cable entry and secure cables to the control base strain reliefs. Discharge static before touching electronics.

  1. Touch a grounded object such as a heating or water pipe before working on electronic modules.
  2. Remove the existing cable grommet when using larger cables.
  3. Plug the grommet into the lower casing section (black) and secure the cable.
  4. Route all connecting cables to their areas and secure them to the control base strain reliefs.

Route low-voltage and 120 V connecting cables

Viessmann · Vitodens 200-W B2HB wiring

Keep cables clear of hot components, since they will be damaged if touching them. Cables must stay within their rated temperature.

  1. Route low-voltage cables and 120 V cables to their connection areas.
  2. For larger cable sizes (up to 9/16 in.), remove the existing cable grommet and secure the cable with the grommet in the lower (orange) casing section.
  3. Secure all cables to the control base using the existing strain reliefs.
  4. Keep the power cable grommet in place for the 120 V connections.

Routine checks by the owner

Viessmann · Vitodens 200-W and Vitocrossal 300 CU3A

Check that flue passages are not blocked, check the system water pressure on the gauge, look for water or rust on flue pipes and vent terminals, and keep combustion air openings clear of chemicals and flammable materials.

  1. Check the vent or chimney for blockage.
  2. Check the pressure gauge reads the correct system water pressure.
  3. Look for water on the floor, leaks at joints and valves, and rust on flue pipes.
  4. Make sure nothing blocks combustion and ventilation air.

Routine safety checks for the vent and system

Viessmann · Vitodens 100-W B1HE/B1KE

Regular checks keep flue gases from leaking into the building and catch water leaks early.

  1. Check the vent or chimney for debris or blockage. Have any blockage removed by a qualified heating contractor.
  2. Check flue pipes, joints, vent dampers and side wall terminals for moisture, water or rust.
  3. Check the pressure gauge for correct system (water) pressure.
  4. Check for water on the floor from the pressure relief valve discharge or any pipe, joint, valve or air vent.
  5. Make sure nothing blocks combustion and ventilation air, and that no chemicals, gasoline or flammable materials are stored near the boiler.

Routing and securing the connecting cables

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Cables must not touch hot components, as they will be damaged. Keep cable temperatures within the maximum permitted for the cable. Use the existing strain reliefs on the control base to secure the cables. For larger wire, remove the existing cable grommet and secure the cable with the grommet fitted in the lower (orange) casing section. The cable size figure in the manual is partly garbled and is not reproduced here.

  1. Discharge static by touching grounded piping before working on electronic modules.
  2. Remove the existing cable grommet if using larger wire.
  3. Route all connecting cables to their areas and secure them to the control base at the existing strain reliefs.
  4. Plug the DHW temperature sensor into the quick connect plugs on the cable harness.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.