Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Replacing the electronics board

Viessmann · Vitotronic 100 GC1 electronics board, Part 7828 193

The electronics board holds the microprocessor and software. Codings must be saved before swapping the board.

  1. Write down all codings and settings on the control unit.
  2. Replace the electronics board.
  3. Set coding 8A: 176.
  4. Set coding address 92 (not in the overview) to 92: 160.

Required codes for installation

Viessmann · Installation

Follow local codes first. Where none apply, use the codes listed in the manual for gas, oil, electrical and controls.

  1. For gas in Canada use CAN/CSA-B149.1 or .2; in the US use NFPA/ANSI Z223.1 (National Fuel Gas Code).
  2. For oil in Canada use CSA B-139; in the US use NFPA 31.
  3. For wiring in Canada use CSA C22.1 Part 1; in the US use NFPA 70 (NEC).
  4. Comply with ANSI/ASME CSD-1 where the authority having jurisdiction requires it.
  5. Use the latest editions of all codes.

Required system type and expansion tank

Viessmann · Vitocrossal 300 CA3B Dual Fuel

The boiler is only approved for closed loop hot water heating systems. The system needs a pre-charged membrane expansion tank.

  1. Install the boiler only in a closed loop hot water heating system.
  2. Make sure the system has a pre-charged membrane expansion tank.

Resetting coding to factory condition

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Returning the coding to the factory condition also clears the LON participant number, so it must be set again.

  1. Note the current LON participant number before changing the coding.
  2. Set coding 77 back to the number needed for each boiler section (1, 2, 3 for sections 1 to 3).
  3. Check the other coding addresses against the factory column.

Restart the start-up wizard after a setup error

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

Use this after a setup error or after adding system components. Record existing settings first, because some may reset during the wizard.

  1. Press OK and menu together for about 4 seconds.
  2. Select Service Functions.
  3. Select Set-up Wizard.
  4. Select Yes.
  5. Press OK to restart the start-up wizard.

Restarting after extended shut-down

Viessmann · Vitorond 200 VD2A boilers

Recondition the system before restarting after a long outage.

  1. Check cold fill pressure and make sure the system is properly vented.
  2. Set the automatic feed valve to the desired fill pressure.
  3. For oil burners, do not reset the burner flame safeguard control more than two times.
  4. If you smell gas, do not touch electrical switches or open flames, open windows, close gas valves, and call the gas supplier from another phone.

Return connection loading on Vitocrossal 300

Viessmann · Vitocrossal 300 with two return connections (system versions 6 and 7)

The lower return connection must receive at least 15% of the boiler's rated output.

  1. Connect at least 15% of the rated output to the lower return connection.

Return water sensor for underfloor heating

Viessmann · Vitotronic 300 KW3 with underfloor heating

In underfloor heating systems, the return water temperature sensor is used so the control can measure both supply and return water temperature.

  1. Install the return water temperature sensor on underfloor heating circuits.
  2. Confirm the control reads both supply and return temperature.

Return water temperature and flow limits with Vitotronic

Viessmann · Vitorond 200 VD2A with Vitotronic control

With Vitotronic controls there is no minimum boiler return water temperature and no minimum heating water flow rate. A shunt pump or low temperature protection package is not needed.

Room sensor placement for RS function remote controls

Viessmann · Vitotrol 200, Vitotrol 300, room temperature sensor

Remote controls with room sensing must be placed where they read a representative room temperature. Remote controls without room sensing (WS function) can go anywhere in the building.

  1. Install the RS remote control on an inside wall of the main living area.
  2. Place it across from radiators, not on shelves, in niches, near doors, or near heat sources such as direct sunlight, fireplaces or TV.
  3. Use a separate room temperature sensor if the remote cannot be placed in a suitable spot.

Room temperature sensor placement

Viessmann · Room temperature sensor, Vitotrol 200A and 300A

Mount the room temperature sensor or remote control in the main living room on an internal wall opposite radiators. Keep it away from shelf units, recesses, doors, and heat sources such as direct sunlight, fireplaces, or TV sets.

  1. Select an internal wall in the main living room opposite radiators.
  2. Keep the sensor out of shelving, recesses, door areas, and direct heat sources.

Room thermostat heat anticipator

Viessmann · Room thermostat wiring

Set the heat anticipator in the room thermostat to match the power requirement of the connected equipment.

  1. Install the thermostat on an inside wall away from drafts, pipes, lighting, sun and fireplaces.
  2. Set the heat anticipator to the value given in the boiler wiring diagram for standard equipment.

Room thermostat installation and heat anticipator

Viessmann · Room thermostat wiring

Mount the thermostat on an inside wall away from drafts, hot or cold pipes, lights, TV, sun and fireplaces. If the thermostat has a heat anticipator, set it to match the load the boiler wiring diagram gives.

Rotary dial address

Viessmann · Versatronik 511 and 511D

The rotary dial sets LON addressing when several gateways are used. Leave it at the factory default of 0 unless a multi-gateway system needs a different setting to avoid duplicate LON addresses.

  1. Leave the rotary dial at 0 for a single gateway.
  2. Set unique dial values only on systems with multiple 511 gateways.

Route and secure field connecting cables

Viessmann · Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125

Keep connecting cables away from hot components, since contact will damage them. Do not exceed the maximum permissible cable temperature. A larger cable (up to 9/16 in.) needs the existing cable grommet removed. Secure the power cable with the grommet seated in the lower orange casing section.

  1. Touch a grounded metal object such as a pipe before handling the electronic modules.
  2. Remove the existing cable grommet if using a larger cable, up to 9/16 in.
  3. Route all connecting cables to their areas (low voltage, 120 V, communication module, DHW sensor plugs).
  4. Secure the cables to the control base using the existing strain reliefs.

Route LON and low-voltage wiring away from mains

Viessmann · Versatronik 511 and 511D LON wiring

Electromagnetic interference can couple onto long wire runs. Keep LON wiring away from 120/240VAC conductors. If that is not possible, use stranded twisted-pair shielded wire and ground only one end of the shield.

  1. Keep LON wires clear of 120/240VAC conductors.
  2. If they must run close, use stranded twisted-pair shielded cable.
  3. Ground only one end of the shield.

Route wiring away from high voltage

Viessmann · Versatronik 515 and 515D gateways

Extended wiring can pick up electromagnetic interference. Keep it away from 120/240VAC conductors. If that is not possible, use stranded twisted-pair shielded wire and ground only one end of the shield.

  1. Keep low-voltage wiring clear of 120/240VAC conductors.
  2. If proximity cannot be avoided, use stranded twisted-pair shielded wire.
  3. Ground only one end of the shield.

Save and activate gateway configuration

Viessmann · Versatronik 585 VI/BACIP

Changes are not used until the configuration is activated. The gateway reboots after you save.

  1. Press SAVE on every configuration screen where you made changes.
  2. Go to the Activate Configuration screen and confirm.
  3. When asked, choose SAVE to store the new settings. The gateway then reboots automatically.
  4. Write down every change you make. The configuration pages can be reached at 192.168.88.89 and at the address you selected.

Select heating circuit before adjusting

Viessmann · Vitotronic 300-K heating circuits

Heating circuit settings apply to the circuit selected on the control, so the correct circuit must be chosen first.

  1. Select the corresponding heating circuit before making any adjustment.

Select the boiler sequence

Viessmann · Vitotronic 300-K MW1S cascade

Set the lead boiler and the boiler sequence in a cascade system.

  1. In coding 2, if required, set coding addresses 39 (permanent lead boiler) and 3A (permanent last boiler).
  2. Press the two buttons shown together for about two seconds.
  3. Select the boiler sequence with the arrow buttons. Pressing both buttons together exits without saving.
  4. Press OK to save the sequence.
  5. In coding 2, set coding addresses 38, 41, 42, 43 and 44 as described in the function description.

Selecting the boiler sequence

Viessmann · Vitocontrol-S VD2/CT3

Sets the boiler sequence on the Vitocontrol-S. Lead and last boiler are set in coding 2.

  1. If required, set coding 2 addresses 39 (permanent lead boiler) and 3A (permanent last boiler).
  2. Press the two buttons shown together for about 2 seconds.
  3. Select the boiler sequence with the up or down button. Press both buttons together to exit without saving.
  4. Press the button shown. The adjustment is transferred.
  5. In coding 2, set addresses 38, 41, 42, 43 and 44 (see function description from page 168).

Sensor capillaries and cable routing

Viessmann · Vitotronic control installation

Sensor capillaries must not be kinked, or the sensors will not work properly. Cables and capillaries must not sit directly on the cast iron heat exchanger.

  1. Keep sensor capillaries straight and unkinked.
  2. Route all cables and capillaries between the nylon-backed insulation and the metal enclosure panels.
  3. Coil any excess cabling and tuck it between the side panel and the insulation.
  4. Tighten the strain reliefs.

Sensor setup at power-up

Viessmann · Versatronik 200 controller

The start-up level for setting the installed sensors shows once after power-on and can be called again by briefly switching the supply off.

  1. Switch the supply voltage off briefly to show the sensor setup level again.
  2. Confirm the installed sensor types before running the system.

Sensor type selection (1 kOhm or 5 kOhm)

Viessmann · Versatronik 200 System Control

Sensors are set to 1 kOhm or 5 kOhm depending on the programming and system selection.

  1. Select the sensor type that matches the programming and system selection.

Service access clearance

Viessmann · Vitorond 100 VR1 boilers

Leave enough room in front of the boiler for cleaning and service. The recommended minimum clearance values are shown in a drawing that does not come through in the text.

  1. Keep at least the minimum service access for cleaning and service.
  2. In an alcove, keep 24 in. (610 mm) free for burner service.
  3. Check the drawing for the recommended minimum service clearances.

Service clearances

Viessmann · Vitodens 200-W B2HA 45, 60 clearances

Zero-clearance to combustibles applies when the boiler is vented with a listed special venting system or CPVC/PP vent. Recommended service clearance is 12 in. (305 mm) on the side, mainly to view the rating plate and fit the PRV kit. Closet and alcove installation is approved. Keep gas ignition components protected from water spray or splashing.

  1. Check the venting system instructions before setting clearances.
  2. Leave 12 in. (305 mm) on the side for rating plate access and the PRV kit.
  3. If the PRV is turned 90° forward with an extension, the side clearance can be reduced; the exact reduced value is not legible in this copy.
  4. Protect gas ignition components from water during operation and service.

Set a static IP address for LAN

Viessmann · LAN connection

The LAN must be connected to the internet for internet access to work.

  1. Open Settings, then 'LAN'.
  2. Select 'Network type'.
  3. Select 'STATIC'.
  4. Confirm.
  5. Enter the IP address, subnet mask, standard gateway, primary DNS server and secondary DNS server.
  6. Confirm.

Set a static IP address for WiFi

Viessmann · WiFi connection

Only needed when the WiFi router does not assign addresses automatically. The router must be set so that addresses are not automatically assigned.

  1. Open Settings, then 'Internet', then 'WiFi'.
  2. Select the network from the available list.
  3. Select network type 'STATIC'.
  4. Confirm.
  5. Enter the IP address, subnet mask, standard gateway, primary DNS server and secondary DNS server.
  6. Confirm.

Set a unique BACnet Device ID and IP address

Viessmann · Versatronik 585 VI/BACIP

Each device needs a unique BACnet Device ID on the whole network. Do not give the gateway an IP address that is already in use.

  1. Open the BACnet Device Settings screen.
  2. Enter a Device ID that is not used anywhere else on the BACnet network.
  3. Set the gateway IP address to a free address on your network.
  4. Press SAVE and then activate the configuration.

Set BACnet device ID and IP before joining the network

Viessmann · Versatronik 300 unit 704092 with BACnet/IP

Applies only to unit 704092 with BACnet/IP. The BACnet Device ID must be unique across the entire BACnet internetwork. Changes do not take effect until Activate Configuration is confirmed.

  1. Connect the Ethernet cable to the BACnet port closest to the middle of the control.
  2. Connect the computer directly to the BACnet port with no other devices attached.
  3. Set the computer to DHCP, or set its IP to 192.168.88.90 with mask 255.255.255.0.
  4. Cycle power on the Versatronik 300.
  5. Browse to http://192.168.88.89/admin and log in.
  6. Change the default password in the Change Password screen if required.
  7. Set the BACnet device settings, pressing SAVE on each screen.
  8. Confirm Activate Configuration and save to reboot.
  9. Write down any changes made, since they are required later.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.