Commissioning: Boiler tips (part 14 of 21)
Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.
Outdoor sensor and DHW limits
Viessmann · Versatronik COMO OT with OpenTherm boiler
The controller works with or without an outdoor sensor. Without a sensor, outdoor reset is not possible and some settings are unavailable. When a sensor is wired in, the controller recognises it automatically. Domestic hot water through the controller only works if the boiler supports a DHW function over OpenTherm.
- Wire the outdoor sensor to terminals 5 and 6 if outdoor reset is wanted.
- Confirm the boiler supports DHW over OpenTherm before expecting hot water production from the controller.
Outdoor sensor and DHW sensor installation notes
Viessmann · Vitodens 100-W B1HE and B1KE
The outdoor sensor is field wired and must sit on the north or northwest wall, 2 to 2.5 m above ground. The DHW tank sensor is an immersion sensor with about 12 ft cable and is supplied ready to plug in. All pipe connections are field supplied.
- Mount outdoor sensor on north or northwest wall, 80 to 100 in. above ground.
- Keep sensor cable clear of line voltage.
- Plug in DHW tank sensor and field-pipe the tank connections.
Outdoor sensor mounting location
Viessmann · Outdoor temperature sensor
The outdoor sensor must be on a specific side of the building at a set height, with its cable kept away from line voltage.
- Mount the outdoor sensor on the north or northwest side of the building.
- Mount it 6.6 to 8.2 ft (2 to 2.5 m) above ground.
- On multi-storey buildings, mount it on the upper half of the second floor.
- Do not lay the sensor cable near 120/240 V wiring.
Outdoor temperature sensor placement and wiring
Viessmann · All Vitocrossal 300 CA3B Dual Fuel models
Mount the outdoor sensor on a north or north-west wall, 6 to 8 ft (2 to 2.5 m) above ground. In multi-storey buildings use the upper half of the second floor.
- Keep the sensor away from windows, doors and vent outlets, and away from balconies or gutters above it.
- Do not paint over the sensor.
- Wire it with 2-conductor cable, 18 AWG, to a maximum length of 115 ft (35 m).
Owner briefing after installation
Viessmann · Vitorond 200 VD2A
The installer must make the system operator or owner familiar with system operation, start-up, shut-down and emergency shut-down, and explain the need for combustion air and regular maintenance.
- Explain the proper system operation sequence.
- Explain the equipment and the need for combustion air.
- Demonstrate an emergency shut-down and state what to do and what not to do.
- Explain that proper maintenance is needed for safe operation.
- Tell the owner where the literature is kept on site.
Owner handover and initial start-up duties
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
The installer must show the owner how the system works, how it is switched on and off, and how to shut it down in an emergency. Initial start-up must be done by a qualified heating contractor, who also completes the maintenance record.
- Explain the operating sequence and the need for combustion air.
- Demonstrate emergency shutdown and state what to do and what not to do.
- Explain that regular maintenance is required for safe operation.
- Complete the maintenance record (page 158 of the manual).
Owner handover and initial start-up requirements
Viessmann · Vitodens 200-W B2HB 19 to 125
The installer must walk the owner through system operation, the equipment, and a manual emergency shutdown. Initial start-up must be done by a qualified heating contractor, and the Maintenance Record must be filled in. The boiler has no user-serviceable parts. Leave the literature on site.
- Show the owner the proper operating sequence and explain the equipment.
- Demonstrate emergency shutdown, including what to do and what not to do.
- Tell the owner that regular maintenance is required for safe operation.
- Complete the Maintenance Record after initial start-up.
- Leave all literature at the site and tell the owner where it is kept.
Oxygen diffusion barrier in underfloor tubing
Viessmann · Vitodens 222-F, B2TB 68 and 125
Boiler warranty does not cover leaks from corrosion caused by underfloor plastic tubing without an oxygen diffusion barrier. Non-barrier tubing must be separated from the boiler with a heat exchanger. Use barrier tubing where possible.
- Use underfloor plastic tubing with an oxygen diffusion barrier.
- If non-barrier tubing is used, separate it from the boiler with a heat exchanger.
Piping and pump sizing are the installer's responsibility
Viessmann · All system layouts
The layout drawings are conceptual only. The heating contractor must verify all piping, components and pump sizing in the field. Undersized pumps or small DHW piping can cause short-cycling and poor DHW supply.
- Verify all piping and components in the field before using any layout drawing.
- Use at least 1¼ in. pipe for DHW supply and return between the boiler and the Viessmann DHW tank.
- For non-Viessmann DHW tanks, calculate the coil pressure drop against the field pump's residual head.
- Check boiler heat exchanger flow against the pressure drop table on page 30.
- Install a low water cut-off where local codes require it.
Piping and system requirements
Viessmann · All models
Rules for the hydronic and gas piping.
- Use only fully pumped hot water systems.
- Never install 4-way mixing valves, overflow valves or flow/return bypass devices.
- Never connect a heating return to the safety return.
- Keep gas ignition components protected from water spray and splashing.
- Ensure gas line is large enough so no pressure drop occurs when any appliance lights or runs.
- Do not install the boiler where the piping interferes with serviceable parts.
Post-installation checklist
Viessmann · Vitotronic 300 KW3
Check these items before start-up and correct any faults.
- Confirm limit capillaries and sensors are fully inserted in the sensor wells.
- Confirm all electrical connections are correct and secure.
- Confirm the boiler coding card is inserted.
- Confirm fuse F2 is plugged in.
- Confirm the outdoor sensor is mounted correctly and cabled to the sensor and connector.
- Confirm the fixed and adjustable high limits are set as required.
- Label the programming unit fields according to heating circuit allocation.
- File the installation, operating and service instructions in the service binder.
Post-installation checklist for the Vitotronic 300
Viessmann · Vitotronic 300 KW3
Before leaving the job, confirm the wiring, sensors and boiler coding card are right and that the control is set up for the heating circuits present.
- Check that the limit capillaries and sensors are fully seated in their wells.
- Check that all electrical connections are made correctly and every connector is fully plugged in.
- Confirm the boiler coding card is inserted.
- Confirm fuse F2 is plugged in.
- Confirm the outdoor temperature sensor is mounted correctly and its cable is properly connected at the sensor and at the connector.
- Set the fixed high limit and the adjustable high limit correctly, if required.
- Label the programming unit fields to match the heating circuit allocation.
- Carry out start-up and adjustments using the Service Instructions.
Power supply and grounding for the Versatronik 503
Viessmann · Versatronik 503 power connection
The module ships with a 6 ft (2 m) power cord with a plug. Electrical work must follow local code and the listed standards. Bond the appliance and pipework to the building's equipotential bonding, and do not swap L and N.
- Protect the power cable with a maximum 15 A breaker.
- Connect the power supply and provide grounding, including an RCD circuit where required.
- Make sure the building grounding and equipotential bonding are connected to the appliance and pipework.
- Keep L and N correctly matched; never swap them.
- Check phase equality against the control unit supply and confirm the phase sequence.
- If extra wire is run, keep it away from 120/240 VAC conductors. Use stranded twisted-pair shielded wire where that cannot be avoided, and ground only one end of the shield.
Power supply and input wiring
Viessmann · Versatronik 300 power input
The control has a 120VAC, 10A rating and comes with a power cord. Finish all low-voltage and output wiring before plugging it in. Do not run the power outlet through a switch or a low water cut-off. A heavy pump may need its own dedicated 120VAC circuit.
- Complete low-voltage and output wiring first.
- Plug the control into a standard 120VAC outlet.
- Do not put a switch or low water cut-off in the power supply to the outlet.
- If the pump load is heavy, feed the control from a dedicated 120VAC source.
Power supply and overcurrent protection
Viessmann · Versatronik 10.WB1 power supply
The 120 VAC supply needs a disconnect switch located outside the boiler room and maximum 15 A overcurrent protection (fuse or breaker). Wiring must follow CSA C22.1 Part 1 or NEC ANSI/NFPA 70 and local codes.
- Install a disconnect switch for the 120 VAC supply outside the boiler room.
- Protect the 120 VAC supply with a fuse or breaker rated 15 A maximum.
- Wire according to CSA C22.1 Part 1 or NEC ANSI/NFPA 70 and local code.
Power supply for the external accessories box
Viessmann · Vitodens 200-W B2HA 45, 60
The external accessories connection box needs a 120 VAC, 12 A supply. Wiring diagram is referenced on page 44, which is not in this extract.
- Provide a 120 VAC, 12 A supply to the external accessories connection box.
- Check the wiring against the wiring diagram on page 44.
PP(s) vent system requirements
Viessmann · PP(s) venting
PP(s) is rated for a maximum of 230 F (110 C). Do not mix components from different vent makers. Flexible vent or air intake pipe reduces the allowed equivalent length by 25 percent. Vent that passes outside the building must be in an enclosed, insulated and waterproof chase.
- Use only ULC S636 / UL-1738 listed PP(s) components.
- Do not mix pipe, fittings or joining methods from different vent manufacturers.
- Check the equivalent length against the two-pipe limits on p. 58 or the single-pipe limits on p. 63.
- Reduce the maximum equivalent length by 25 percent when flexible pipe is used.
- Install a side wall vent with a protective screen.
Pressure relief valve discharge and isolation rules
Viessmann · Vitodens 222-F, B2TB
Keep the relief discharge safe and never isolate the relief valve from the boiler.
- Do not install an isolation valve between the boiler and the pressure relief valve.
- Orient the discharge pipe so it cannot scald people.
- Pipe the discharge close to a floor drain.
- Never pipe the relief discharge to the outdoors.
Pressure relief valve installation and discharge piping
Viessmann · Vitocrossal 200 CI2 399 to 2000
The pressure relief valve mounts on the top of the boiler or on the boiler safety supply. Nothing that can shut off or block flow may be between the boiler and the relief valve or on its discharge side. The discharge pipe keeps the same size as the outlet, runs horizontally over the side of the boiler and then down to about 1 ft (300 mm) above the floor, as close to a floor drain as possible. Do not pipe the discharge outdoors or to any place where it can freeze.
- Mount the relief valve on the top of the boiler or the boiler safety supply.
- Do not install any valve or obstruction between the boiler and the relief valve.
- Keep the discharge pipe the same size as the relief valve outlet.
- Run the discharge horizontally over the side of the boiler, then vertically down to about 1 ft (300 mm) above the floor.
- Route the discharge close to a floor drain and not outdoors or where freezing can occur.
- Secure the discharge piping with hangers or brackets.
Primary waterside flow and low-loss header
Viessmann · Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125
The boiler is for closed-loop, forced-circulation hot water systems only. Size pipe with the standard friction loss method and stay within the boiler flow limits. Viessmann strongly recommends a low-loss header (LLH) and prefers it over closely spaced tees. If system flow is unknown or outside the boiler limits, use an LLH.
- Size the primary piping with the standard friction loss method.
- Confirm system flow is within the boiler minimum and maximum limits.
- Install a low-loss header if flow is above the maximum, below the minimum, or unknown.
- Connect the low-loss temperature sensor (80/60) for single-boiler applications.
Pump selection and low-loss header logic
Viessmann · Vitodens 222-F, B2TB 68 and 125
Pump selection must be based on accurate system flow and pressure drop calculations, including DHW sizing. The boiler has a factory-set integrated boiler/system pump, and its flow must be selected based on Ut. With a low-loss header connected, the boiler's built-in LLH logic manages Ut through sensor communication with the header.
- Calculate system flow and pressure drop, including DHW sizing.
- Confirm system flow is within boiler max and min flow limits.
- Install a low-loss header if flow exceeds max, falls below min, or is unknown.
- Connect the Viessmann low-loss temperature sensor for single-boiler use.
Pump selection for field-supplied pumps
Viessmann · Heating circuit pumps
The boiler is only for closed-loop, forced-circulation hot water systems. Size field pumps on pressure drop from accurate system flow and head calculations, including DHW sizing.
- Calculate system flow and pressure drop, including DHW load.
- Size pipe with the standard friction loss method.
- Keep flow within the boiler's maximum and minimum limits.
Pump sizing for underfloor layouts
Viessmann · Vitocrossal 300 CU3A system layouts 2, 3 and 4
In system layouts with mixing valves, the field-supplied pump size controls proper boiler operation.
- Size the field-supplied pump using the boiler supply head pressure drop given on page 8 of the manual.
- Do not undersize the pump, which can cause short cycling or poor boiler operation.
- Check the pressure drop of the plate heat exchanger on the secondary side is not greater than the pressure drop of the 3-way mixing valve.
Pump wiring with motor contactors or starters
Viessmann · Vitotronic 100 GC1 pump connections
Single-phase and three-phase pumps must be connected through field-supplied motor contactors or motor starters.
- Install field-supplied motor contactors or motor starters for single-phase and three-phase pumps.
Purge LPG supply
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
Purge the LPG tank and gas supply line during commissioning or replacement.
- Purge the LPG tank and gas supply line twice during commissioning or replacement.
Recall the commissioning assistant later
Viessmann · Vitocrossal 200 CI2, all sizes
The commissioning assistant can be restarted at any time if commissioning must be finished later.
- Tap the menu button.
- Select Service.
- Enter password viservice and confirm.
- Select Commissioning and confirm.
Record slab curing heat-up data for the report
Viessmann · Slab curing function (coding address F1)
The contractor report for slab curing needs the heat-up data.
- Record the heat-up supply temperatures for each step.
- Record the actual maximum supply temperature reached.
- Record the operating condition and outdoor temperature at handover.
- Follow the slab supplier's instructions and DIN 4725-2 or local rules.
Record technical data at initial start-up
Viessmann · Vitorond 200 VD2A boilers
Values and calibrations in the Technical Data section must be recorded during the first start-up.
- Record the values and calibrations from the Technical Data section (page 38) at initial start-up.
- Explain the sequence of operation, combustion air needs, emergency shut-down, and the need for annual maintenance to the owner.
Red wire on Riello and Carlin burners
Viessmann · Riello and Carlin burner wiring
The red wire is not used in this application.
- Use wire nuts to cap both ends of the red wire: inside the high limit control and at the Riello burner sub-base.
Replacing the control printed circuit board
Viessmann · Line voltage and low voltage motherboards
Before the board is swapped, the coding must be saved, because the new board needs its coding restored.
- Record all coding and adjustments made at the control unit.
- Replace the printed circuit board.
- Set coding 8A: 176.
- Set coding address 92 to 92: 160.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.