Access & passwords: Boiler tips (part 4 of 4)
Short, practical technician tips on access & passwords for boiler. Check each one against the manual for your exact model before acting.
Panel removal for lag controls, service displays and emissions test switches
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Emissions test switches D, E and F are behind the front top and bottom panels and control covers. For the 2nd to 4th boiler, the lower front panel and control cover must be opened to set up lag control. Single-boiler setups need no panels opened.
- Open the front top and bottom boiler panels and control covers to reach the emissions test switches D, E and F.
- For lag control on the 2nd to 4th boiler, open the lower front panel and control cover.
- For a service condition on B or C, open the lower front panel and control cover.
- For a service condition on A, open the top front panel and control cover as needed for the fault.
Reaching coding levels and resetting coding
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Coding is reached through the Service menu with a password. Coding level 1 uses the viservice password; coding level 2 uses viexpert. Resetting coding restores factory values for the chosen group.
- From the home screen, open Service and enter the viservice password.
- Open System coding (or System configuration) and select Coding level 1.
- For Coding level 2, enter the viexpert password instead.
- To reset, select Reset coding address.
- To change a single value, select the group and coding, then choose the required value from the table and accept it.
Read the fault history from the control unit
Viessmann · Vitotronic control unit with graphical user interface
The 10 most recent faults are stored, including faults already fixed. They are sorted by date.
- From the home screen, open the Service menu.
- Enter the password viservice.
- Open Fault history.
- Tap the entry to see more detail on that fault.
- Use the delete function to clear the list.
Removing and reinstalling the top panel
Viessmann · Vitorond 100 boiler casing
The top panel screw can make the panel hard to remove. Moving the screw helps.
- Move the top panel screw about 3 in. to the left or right.
- Pre-drill the panel with a 1/8 in. bit to make the new mounting hole.
- When reinstalling, drill a new 1/8 in. pilot hole through the top back panel and into the back panel, then fit screw P in the new hole.
Return to the standard menu
Viessmann · Vitotronic control unit, standard menu
Use this to get back to the standard menu from the screen saver or from any point inside the menu.
- If the screen saver is active, press any key except the one shown as ?.
- If you are somewhere in the menu, keep pressing until the standard menu appears.
Return to the standard menu or open the extended menu
Viessmann · Vitocrossal 300 CU3A with Vitotronic control
Press any key except the info key to leave the screen saver, or keep pressing until the standard menu appears. The extended menu holds less-used settings such as time and holiday programs.
- If the screen saver is active, press any key except the info key, then press the menu key to open the extended menu.
- If already in a menu, keep pressing the back key until the standard menu appears.
- Use the extended menu for other connected heating circuits.
Scan system information
Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C
Opens the main information menu. Groups are General, Combustion controller, Heating circuit 1, 2 and 3, DHW, Solar energy, Reset data, Opening source licenses and Service address. Groups shown depend on connected components and settings. Named heating circuits show their assigned name.
- From the home screen, open Menu, then Information.
- Select the group you need.
Service and expert passwords for coding
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Coding is reached from the Service menu. The service password is "viservice". Coding level 2 uses the "viexpert" password.
- From the home screen, open Service.
- Enter the viservice password.
- For coding level 1, open System coding or System configuration.
- For coding level 2, enter the viexpert password.
Service password for commissioning and service menus
Viessmann · Vitocrossal 200 CI2 programming unit
The Service level password is viservice. It is used to open the Service menu and call up commissioning and test mode.
- Open the Service menu.
- Enter password viservice and confirm.
Standard and extended menu access
Viessmann · Vitotronic 200 KW6B
The standard menu covers the primary heating circuit. The extended menu covers all control functions. The heating contractor can block either menu, and if blocked, only service and fault messages can be viewed.
- From the screen saver, press OK to open the standard menu.
- To open the extended menu from the standard menu, press the menu key.
- From anywhere in the menu, hold the key until the standard menu appears to go back.
- Select the heating circuit before changing its settings, since settings apply per heating circuit.
Standard and extended menu on the Vitotronic 300-K
Viessmann · Vitotronic 300-K MW1B
The control has two levels: the standard menu and the extended menu. Your heating contractor can block the extended menu, in which case you can only scan fault messages. In the standard menu the boilers are shown in boiler sequence. A solid white icon means the boiler is enabled by the cascade control and running. A solid grey icon means the boiler is available but not enabled. A solid black crossed-out icon means the boiler is not available for heat production. The display returns to the standard menu about 2 minutes after the last setting.
- From the screen saver, press OK to reach the standard menu.
- From any screen, hold the back key until the standard menu appears.
- To reach the extended menu from the standard menu, press the extended menu key.
- Expect the extended menu to be locked if the fault scan is the only option shown.
Unlock the controls
Viessmann · Control panel
When the panel is locked, 'Panel locked' appears after tapping any on-screen button.
- Tap any on-screen button. 'Panel locked' is displayed.
- Confirm that you want to unlock the operation.
- Enter the password 'viessmann' or your own password.
- Confirm.
Unlock user interface and select language
Viessmann · Vitodens 200-W B2HA 19, 28, 35
The control display is in German at commissioning. Unlock the programming unit covers before changing the language.
- Turn both locks up to unlock the user interface programming unit covers.
- Slide the covers open.
- Turn the boiler on with the ON/OFF switch.
- On the Sprache (Language) screen, select the language and press OK to accept.
- To change later: extended menu, Settings, Language, select, then OK.
Wake the screen and open the home screen
Viessmann · Vitotronic 300 GW6C service display
The touchscreen sleeps after a period of no use. Tap the display to wake it. From any menu level, use the home button to return to the home screen.
- If the screensaver is on, tap anywhere on the display.
- From any menu, tap the home button in the footer.
Waking the touchscreen and opening the menu
Viessmann · Vitocrossal 300 CA3B service display
The service display has a touchscreen and goes into a screensaver after a period of no use. Wake it by tapping the display, then tap Menu to open the main menu. The main menu is used for settings and scans.
- If the screensaver is active, tap the display anywhere, then tap Menu.
- From any other screen, tap the home button in the footer, then tap Menu when needed.
WiFi access code labels
Viessmann · Vitodens 100-W with WiFi module
WiFi access code labels are on the back of the programming unit.
- Before installing the programming unit, remove the access code labels from its rear. Three copies are there.
- For commissioning, put one label on the front of the boiler.
- Put one label where it can be found later, such as the operating instructions.
- Switch WiFi on and connect to the router to use the app.
Access contractor menus
Weil-McLain · ECO Tec control
Contractor menus are opened from the home screen with a press-and-hold on the WM logo.
- From the home screen, press and hold the WM logo for 7 seconds.
- Choose the contractor menu item needed, such as BOILER SETTINGS, SYSTEM SETTINGS, DIAGNOSTICS or SERVICE INFO.
Access Modbus settings for BMS
Weil-McLain · Evergreen Pro control with BMS
Modbus settings are in the contractor menu. Adjust them to match the BMS.
- From the home screen, press and hold the WM logo to open the contractor menu.
- Open the Modbus Setting screen.
- Set all Modbus values to match the BMS being used.
- If the BMS uses BACnet, install a BACnet converter between the BMS and the JP4 Modbus terminals.
Accessing the contractor menus
Weil-McLain · ECO Tec control, home screen
Contractor menus are opened from the home screen by pressing and holding the WM logo for 7 seconds.
- From the home screen, press and hold the WM logo for 7 seconds.
- Navigate to the contractor menus.
Enter contractor menus
Weil-McLain · Unity control, SVF Series 1
Contractor menus are reached by holding the UP and DOWN arrow keys together. Settings are changed from there.
- Press and hold UP and DOWN together for 7 seconds.
- Work through the menu sequence (see Figure 66 on page 74 for the path to the CONTRACTOR menu).
Enter installer menus
Weil-McLain · ECO Tec Series 3 80/110/150/199
Installer menus are opened from the Homeowner screen.
- On the Homeowner screen, press and hold the WM logo at top left for 5 seconds.
Enter the contractor menus on the U-Control
Weil-McLain · Ultra U-Control, all Ultra Series 4 sizes
The contractor menus are hidden behind a hold-to-enter key combination. The top screen lists BOILER SETTINGS, SYSTEM SETTINGS, DIAGNOSTICS, MAINTENANCE INFO and SET DATE AND TIME.
- Press and hold the UP and DOWN arrow keys together for 5 seconds.
- Use the arrow keys to move through the contractor menus.
- Follow the instructions at the bottom of each screen to move to the next or previous screen, or to enter and save data.
Enter U-Control installer menus
Weil-McLain · U-Control on Ultra Series 4 boilers
Installer menus are opened from the boiler control display.
- Press and hold the UP and DOWN arrow keys together for five seconds.
Open the contractor menus
Weil-McLain · Evergreen Series 2 with Evergreen Pro control
The contractor menus are hidden behind the home screen and are reached by holding the WM logo.
- From the home screen, press and hold the WM logo for seven seconds.
- Select BOILER SETTINGS, SYSTEM SETTINGS, PUMP SETTINGS, NETWORK SETTINGS, DIAGNOSTICS or SERVICE INFO as needed.
Open the U-Control installer menus
Weil-McLain · U-Control on Ultra Series 4
Installer menus are opened from the control keypad by holding the UP and DOWN arrows.
- Start a call for heat on one of the heat demand inputs.
- Press and hold the UP and DOWN arrow keys together for five seconds.
- Use the display to navigate to the setting or test you need.
USER MENU items
Weil-McLain · Evergreen Pro control display
The USER MENU is used for date and time and for resetting faults. Its items include Date/Time, Backlight, Clean, Software, Bluetooth, Maintenance and Settings. Hot Water and Network appear on the menu but are not described on these pages.
- Date/Time: edit the date, time and daylight savings time.
- Backlight: set screen brightness during normal operation and when dormant.
- Clean: locks the screen for 10 seconds for cleaning.
- Software: shows control and display software revisions.
- Bluetooth: turn Bluetooth on or off.
- Maintenance: view contractor and maintenance information and reset the reminder.
- Settings: edit temperature units, screen timeout and press sound effects.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.