Navien General: Replacing the main solenoid valve

Updated · by Aurora Star Tech Inc.

Replacing the main solenoid valve on a Navien general: Main solenoid valve is an NC (normal closed) type on the inlet water pipe assembly. The water support frame and bypass valve must be moved to reach it.

Homeowner with a heating or cooling system problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: WEC600

How to fix replacing the main solenoid valve: step by step

  1. Shut off the feedwater supply.
  2. Disconnect power to the WEC.
  3. Remove the back cover (see Removing the Back Cover, p. 82).
  4. Remove 2 screws from the water support frame and unplug its connector.
  5. Lift the water support frame out of the WEC.
  6. Remove 6 screws from the front frame bracket.
  7. Unclip and unplug the hose and connector from the freeze prevention solenoid valve.
  8. Remove 2 L-clips and the connector from the bypass valve assembly and pull the bypass valve out of the WEC.
  9. Remove the L-clip and connector from the main solenoid valve and pull it out of the inlet water pipe assembly.
  10. Install the new NC type solenoid valve on the inlet water pipe assembly and secure its L-clip and connector from the harness.
  11. Install the bypass valve assembly on the inlet water pipe and secure its 2 L-clips and connector.
  12. Reconnect the hose and connector to the freeze prevention solenoid valve and secure the clip.
  13. Secure the front frame bracket with 6 screws.
  14. Insert the water support frame into the sliding bracket at the bottom of the WEC, connect its connector, and secure with 2 screws.
  15. Put the back cover on and secure with 11 screws.
  16. Remove the front and top covers to reach the DIP switches on the main panel (steps 3-5 in 8.2 Replacing the Power Assembly, p. 83).
  17. Check DIP switch 2 and set it to OFF if it is ON.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien General codes

Source: Navien WEC Series service manual, p. 107-109. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.