Navien General: Replacing the flow sensor
Replacing the flow sensor on a Navien general: Remove the back cover and the outlet water pipe assembly to reach the flow sensors, then replace them and reassemble.
Applies to: WEC600
How to fix replacing the flow sensor: step by step
- Turn off the feedwater supply.
- Disconnect power to the WEC.
- Remove the back cover (see page 82).
- Remove the 4 L-clips from the Y-adapter and T-adapter.
- Remove the 2 screws holding the outlet adapter bracket and pull the outlet water pipe assembly out of the water treatment system.
- Remove the 4 clips and unplug the 2 flow sensor connectors from the outlet water pipe assembly.
- Fit the new flow sensors to the outlet water pipe assembly, secure them with 4 clips, and reconnect the 2 flow sensor connectors to the harness.
- Place the water pipe assembly back on the WEC and secure it with 2 screws at the outlet adapter.
- Fit the 4 L-clips onto the Y-adapter and T-adapter.
- Reinstall the back cover and secure it with 11 screws.
If the unit shows an error code, look it up: Navien General codes
Source: Navien WEC service manual, pp. 94-95. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.