Navien Furnace: Wire a dehumidistat to the sub controller
Wire a dehumidistat to the sub controller on a Navien furnace: Dehumidistat must run on 24 VAC and use a switch that opens when humidity rises. During a combined cooling and dehumidification call the blower runs at about 85% of the desired speed.
Applies to: NPF700 Hydro-furnace with optional dehumidistat
How to fix wire a dehumidistat to the sub controller: step by step
- Turn off power to the furnace.
- Connect the dehumidistat neutral wire (usually white) to the DEH terminal on the sub controller.
- Connect the dehumidistat hot wire (usually black) to the R terminal on the sub controller.
- Connect the dehumidistat ground wire (usually green) to the ground screw on the junction box, if present.
- Restore power and turn on the dehumidification function on the front control panel.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.