Navien Furnace: Venting method overview (Category IV FSP)
Venting method overview (Category IV FSP) on a Navien furnace: This furnace is certified as a Category IV Type FSP furnace for non-direct and direct vent installations.
Applies to: NDF600 series furnaces
How to fix venting method overview (category iv fsp): step by step
- For direct vent, supply all combustion air from outdoors through the plastic piping system; the 2 in PVC connector to the furnace is the only furnace-supplied component.
- Use the adapter gasket supplied with the combustion air adapter and keep the combustion air piping airtight.
- For non-direct vent with indoor combustion air, only a vent pipe is required and combustion air routing is not provided.
- Direct vent is the preferred method because it avoids using heated room air for combustion and is unaffected by exhaust fans or other negative pressure devices.
- If the furnace is installed near other fuel burning appliances, confirm there is adequate combustion air for the non-direct vent appliance.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.