Navien Furnace: Vent termination clearances in Canada
Vent termination clearances in Canada on a Navien furnace: Minimum distances for the vent exhaust terminal in Canada.
Applies to: NDF600 series furnaces, installations in Canada
How to fix vent termination clearances in canada: step by step
- Do not terminate directly above a paved sidewalk or driveway between two single-family dwellings that serves both.
- Keep at least 7 ft (2.1 m) above a paved sidewalk or driveway on public property.
- Keep at least 6 ft (1.8 m) from any mechanical air supply inlet to a building.
- Above a meter/regulator assembly, stay at least 3 ft (0.91 m) horizontally from the regulator centerline.
- Keep at least 3 ft (0.91 m) from any service regulator vent outlet.
- Keep at least 12 in (305 mm) above grade or anticipated snow level.
- Keep at least 12 in (305 mm) from any door, window or non-mechanical air supply inlet.
- Keep at least 12 in (305 mm) from the combustion air inlet of any other appliance.
- Do not terminate underneath a veranda, porch or deck unless it is fully open on at least two sides beneath the floor and the vent top is more than 12 in (305 mm) below its underside.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.