Navien Furnace: Using the furnace as a construction site heater
Using the furnace as a construction site heater on a Navien furnace: The furnace may be used during construction only if all the listed conditions are met.
Applies to: NPF700 series
How to fix using the furnace as a construction site heater: step by step
- Permanently install the vent system per the installation instructions.
- Control the furnace with a room thermostat. Fixed jumpers that force continuous heat must not be used.
- Provide sealed return air ducts to the furnace.
- Keep the return air temperature between 60 °F (16 °C) and 80 °F (27 °C).
- Install air filters during construction, replace them as needed, and replace them at completion.
- Set the input rate and temperature rise per the rating plate.
- Supply 100% outside air for combustion during construction. Temporary ducting may be used but must not connect directly to the furnace.
- Size temporary ducting per NFPA 54/ANSI Z223.1 or CAN/CSA B149.1.
- Clean the heat exchanger, components, ducts, filters and evaporator coils after final construction cleanup.
- Verify ignition, input rate, temperature rise and venting per the installation instructions.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.