Navien Furnace: Horizontal exhaust and combustion air termination layout
Horizontal exhaust and combustion air termination layout on a Navien furnace: Terminal geometry for horizontal venting to keep flue gases from recirculating into the intake.
Applies to: NDF600 series furnaces, horizontal direct and non-direct vent
How to fix horizontal exhaust and combustion air termination layout: step by step
- Terminate the vent at least 8 in (203 mm) from the wall.
- Use a medium or long sweep 90 degree elbow pointing downward on the combustion air intake to keep out rain.
- Exhaust may end in a tee, 45 degree elbow, or medium or long sweep 90 degree elbow pointing within 45 degrees of downward, away from the intake.
- If clearance to grade cannot be met with straight-through piping, periscope the pipe up to 24 in (610 mm) using the same pipe size, counting the fittings and length in total vent length.
- If winter winds may blow flue gases back into the intake, raise the exhaust 18 to 24 in (457 to 610 mm) above the combustion air intake terminal.
- Insulate exterior vent pipe 24 in (610 mm) or longer with 1/2 in (13 mm) insulation.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 27, 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.