Navien Furnace: Gas type and high altitude conversion procedure

Updated · by Aurora Star Tech Inc.

Gas type and high altitude conversion procedure on a Navien furnace: Converting the furnace to propane or to high altitude natural gas. Use only the Navien conversion kit for the job. Tools needed: Phillips and flathead screwdrivers, 5/32 in or 4 mm Allen wrench, combustion analyzer or dual port manometer, gas leak detector.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NPF700 series furnaces (natural gas to propane or high altitude natural gas)

How to fix gas type and high altitude conversion procedure: step by step

  1. Turn off power, gas and water supply (if a supply valve is used). Let the furnace cool if it was running.
  2. Loosen the knobs on the upper front cover counterclockwise, remove them, then remove the cover.
  3. With the internals exposed, find the gas inlet pipe and gas valve.
  4. Remove the two screws at location A, where the gas valve connects to the gas valve outlet adapter.
  5. Remove the two screws at location B, where the gas valve connecting pipe attaches to the single venturi, then pull the pipe away from the fan assembly.
  6. Remove the two screws holding the gas orifice in the fan assembly, then take out the orifice.
  7. Check the O-ring between the gas valve and its inlet adapter. It must be in good condition and installed; replace it if needed.
  8. Seat the gasket in the port, then install the new orifice from the correct conversion kit. Confirm the orifice sits properly on the gasket.
  9. Reinstall the gas valve outlet adapter and all screws. Do not overtighten.
  10. Set DIP switch 1 for the new gas type (ON for propane, OFF for natural gas).
  11. Turn the gas and water supply back on.
  12. Check the gas/air ratio with a combustion analyzer (recommended) at the analyzer port, or by the other method in the manual, against the CO2 values in Table 2. Keep CO2 within 1.0% of the listed value.
  13. Set the installation altitude on the front control panel.
  14. Reinstall the upper front cover and check that the furnace runs normally.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Furnace codes

Source: Navien NPF Condensing Hydro-furnace installation and operation manual, p. 131 to 136. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.