Navien Furnace: Gas shut-off valve placement and pressure test limits
Gas shut-off valve placement and pressure test limits on a Navien furnace: Place the manual shut-off valve and dirt pocket close to the furnace. Some local codes require the valve between 4 and 5 ft above floor level. Disconnect the manual shut-off valve and gas valve before any pressure test above 1/2 psig (3.45 kPa). Use a backup wrench on the gas valve so it does not twist.
Applies to: Gas supply installation and pressure testing
How to fix gas shut-off valve placement and pressure test limits: step by step
- Install a manual gas shut-off valve and dirt pocket as close to the furnace as possible.
- Check local code for valve height (4 to 5 ft above floor).
- Keep the valve readily accessible.
- Disconnect the manual shut-off valve and gas valve before any test above 1/2 psig.
- Use a backup wrench when tightening so the gas valve is not strained.
If the unit shows an error code, look it up: Navien Furnace codes
More commissioning tips for furnace
Source: Navien NDF installation and operation manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.