Navien Furnace: Convert condensate drain and water connections from left to right
Convert condensate drain and water connections from left to right on a Navien furnace: The furnace ships with the auto water fill connection and junction box on the right side, with the condensate hose set for left side installs. Use this procedure to convert for right side installs.
Applies to: NPF700 Upflow and Downflow Hydro-furnace
How to fix convert condensate drain and water connections from left to right: step by step
- Turn off power and remove the upper front cover knobs (turn counterclockwise), then remove the upper and lower front covers.
- Disconnect the condensate drain hose, junction box, supply water assembly, and drain trap assembly. Loosen hose fasteners with pliers.
- Move the grommets from the left side to the right side: gas pipe, condensate, electrical line, overflow and gas pipe, screw hole, and supply water.
- Replace the drain trap assembly with the included right condensate drain hose and overflow hose. Assemble with the condensate adapter and hose fasteners as shown.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 87-88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.