Navien Furnace: Construction heater conditions
Construction heater conditions on a Navien furnace: The furnace may be used as a construction heater only if the listed conditions are met.
Applies to: NDF600 series
How to fix construction heater conditions: step by step
- Install the vent system permanently per the manufacturer's instructions.
- Supply 100% outdoor air for combustion during construction.
- Keep the furnace under thermostatic control; no fixed jumpers for continuous heating.
- Install MERV 8 or better filters and change or service them daily during construction.
- Seal the return air duct to the furnace.
- Keep return air between 55°F (13°C) and 80°F (27°C) with no evening setback or shutdown.
- Set input rate and temperature rise per the rating plate.
- After construction, clean the furnace and ducts and verify ignition, input, temperature rise and venting.
- Keep furnace doors in place whenever the furnace operates.
If the unit shows an error code, look it up: Navien Furnace codes
More commissioning tips for furnace
Source: Navien NDF installation and operation manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.