Navien Furnace: Connecting the supplied drain hoses to the trap
Connecting the supplied drain hoses to the trap on a Navien furnace: Two hoses connect the front manifold cover and the inducer to the trap assembly. The larger tube goes to the manifold, the smaller tube goes to the inducer. All tubing must slope toward the trap with no kinks or low points.
Applies to: NDF drain hose connections
Common causes of connecting the supplied drain hoses to the trap
- Hose low points or kinks ahead of the trap cause trapped water
How to fix connecting the supplied drain hoses to the trap: step by step
- Connect the 5/8 in. tubing from the most direct drain outlet on the front manifold cover to the larger elbow on the trap.
- Cut excess tubing and secure it with the supplied plastic hose clamps.
- Connect the 1/2 in. tubing from the inducer drain outlet to the smaller elbow on the trap.
- Check that all tubing slopes down toward the trap with no traps or kinks.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF Installation and Operation Manual, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.