Navien Furnace: Check inlet gas pressure (two-stage gas valve)
Check inlet gas pressure (two-stage gas valve) on a Navien furnace: Measure gas inlet pressure with a calibrated U-tube or digital manometer on the inlet pressure boss.
Applies to: Two-stage gas valve inlet pressure
How to fix check inlet gas pressure (two-stage gas valve): step by step
- Turn off gas and electrical supply to the furnace.
- Back the inlet pressure test screw out counterclockwise one turn maximum with a 3/32 in. Allen wrench.
- Attach a hose so it overlaps the boss by 3/8 in. Use a manometer with at least a 0 to 15 in. w.c. range.
- Turn on gas and power. Run the furnace and all other gas appliances on the line.
- Check the pressure boss for leaks with leak detection solution. Repair any leaks.
- Measure inlet pressure with burners firing. It must be within the rating plate range (5 to 10.5 in. w.c. natural, 11 to 13 in. w.c. LP).
- Shut off gas and power. Remove the hose and tighten the inlet pressure screw clockwise to at least 7 in-lb.
- Turn gas back on and leak test the boss again.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.