Updated · by Aurora Star Tech Inc.

CH series gas inlet pressure and gas-air ratio check on a Navien combi boiler: How to check inlet gas pressure and set the gas-air differential on CH boilers. Licensed gas tech only.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series gas inlet pressure and gas-air ratio check

  • Low or high inlet pressure
  • Gas-air differential out of spec after a gas valve or PCB change

How to fix ch series gas inlet pressure and gas-air ratio check: step by step

  1. Gas work: licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
  2. Inlet: shut the gas, run hot water until the unit drops out, then fit a manometer to the inlet test port and zero it.
  3. Open the gas, check for leaks, and open several high-flow taps to reach max fire. Expect NG 6.0-10.5 in. W.C, LP 8.0-13.5 in. W.C.
  4. Gas-air: shut the gas, remove the front panel, connect the manometer high side to the GPS tube and low side to the APS tube. Open the gas and leak test.
  5. DIP 1 ON and 2 ON = 3-stage min. Open a hot tap. Adjust the proportional valve to spec.
  6. DIP 1 ON and 2 OFF = 3-stage max. Run high flow. Adjust with the variable resistor on the PCB.
  7. Spec (NG): CH-180 min 0.86 ± 0.04 / max 2.68 ± 0.08 in. W.C. CH-210 min 0.63 ± 0.04 / max 1.61 ± 0.08. CH-240 and CH-240 ASME min 0.63 ± 0.04 / max 2.13 ± 0.08.
  8. Put the DIP switches back to normal, refit the tubes and the panel. Do this check after any PCB swap.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 6.2 Measuring Gas Pressure Setting p.113-115; 8.2.1 p.118. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.