Navien Combi Boiler: CH series E027 air pressure sensor fault – full check
CH series E027 air pressure sensor fault - full check on a Navien combi boiler: E027 shows if the APS signal is open (about 0.1 V or less) or shorted (about 4.5 V or more) for 3 seconds, or if it already reads 1.20 V before pre-purge.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e027 air pressure sensor fault - full check
- APS connector loose
- Failed APS
- Bad PCB
How to fix ch series e027 air pressure sensor fault - full check: step by step
- Turn off power before unplugging connectors or measuring resistance.
- The code table also says to check the vent pipe for blockage and clean the intake air filter.
- Check the APS plug is fully seated.
- APS supply is 5 V (black + white per the service table).
- Signal with fan off: about 0.2-0.6 VDC. Signal with fan running: about 1-4 VDC (black-white at CN6 per the flowchart).
- Out of range = replace the APS. In range and still E027 = replace the PCB.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.21 27 Error p.98-99. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.