Updated · by Aurora Star Tech Inc.

CH series E016 heat exchanger high limit - full check on a Navien combi boiler: E016 locks the boiler out when the heat exchanger high limit opens at 197°F or more for 1 second. Post-purge runs. Manual reset. Wait at least 30 minutes after the trip before measuring.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series e016 heat exchanger high limit - full check

  • Heating valves closed
  • Heating strainer plugged
  • Pump stuck or dead
  • High limit switch or thermal fuse open
  • Supply thermistor reading low
  • Heat exchanger plugged or failing

How to fix ch series e016 heat exchanger high limit - full check: step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check heating supply/return valves are open.
  3. Clean the heating strainer and find where the debris comes from.
  4. Check the pump runs (free the shaft, check power, capacitor, coil). No power = PCB.
  5. Wait 30 min, then check the high limit: should read 0 ohm. Infinite = bad. The manual names CN13 white pair for E016 and brown pair for E030.
  6. Check the thermal fuse for continuity. If blown, replace it and find why it blew.
  7. If the supply sensor reads lower than the real water temp, replace it.
  8. Blow through the heat exchanger to check for blockage. If it trips only on hot water, check the DHW heat exchanger.
  9. Overheating surface on the heat exchanger = replace the heat exchanger.
  10. If all checks pass, replace the PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.16 16 Error p.87-89. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.