Navien Combi Boiler: CH series E012 flame loss – full check
CH series E012 flame loss - full check on a Navien combi boiler: If the flame drops out during a burn, the unit relights and counts. After 20 flame losses in a row it shows E012, manual reset.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e012 flame loss - full check
- Low gas pressure (LP drops in winter), small pipe or meter
- Gas-air differential out at 3-stage min
- Wrong DIP capacity setting
- Air pressure sensor reading high
- Dirty nozzles (stage 2/3 cause dropouts when stages switch)
- Multi-stage valve or main valve proportional part faulty
- Bad PCB
How to fix ch series e012 flame loss - full check: step by step
- Gas work: licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
- Inlet pressure at max fire: NG 6-10.5 in. W.C, LP 8-13.5 in. W.C. Check dynamic pressure.
- Gas pipe 3/4 in. or larger. Check gas meter size and the inlet fitting gasket.
- Check the gas-air differential at 3-stage min (DIP 1 and 2 ON). Try the adjusting screw under the gas valve half a turn and watch the flame.
- Check the DIP capacity setting.
- Pull the manifold and clean the nozzles.
- Flame drops when stages switch: check the multi-stage valve.
- Replace the air pressure sensor if it reads high.
- If all checks pass, replace the PCB.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.13 12 Error p.82-83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.