Navien Combi Boiler: CH series E011 high water pressure – full check
CH series E011 high water pressure - full check on a Navien combi boiler: E011 shows when system pressure stays at 56.6 psi or more for 3 seconds. It clears at 43.5 psi or less. If the boiler display shows SEE with E011 on the room controller, the pressure sensor itself has failed.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e011 high water pressure - full check
- Expansion tank failed or waterlogged
- System overfilled
- Relief valve stuck
- Pressure sensor frozen or failed (SEE)
How to fix ch series e011 high water pressure - full check: step by step
- Check system pressure with a gauge. Over about 3.9 bar (56.6 psi) is real high pressure.
- Check the expansion tank charge.
- Do not overfill when topping up. Drain to normal pressure.
- Check the relief valve is not stuck.
- E011 + SEE: check if the sensor froze. Check the sensor plug for open or short. Replace the pressure sensor if bad.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.12 11 Error p.81-82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.