Navien Combi Boiler: CH series E007 / E008 hot water outlet thermistor – full check
CH series E007 / E008 hot water outlet thermistor - full check on a Navien combi boiler: E007 = DHW outlet sensor open (14°F or less). E008 = DHW outlet sensor shorted (248°F or more). Both trigger after 3 seconds.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e007 / e008 hot water outlet thermistor - full check
- Loose or wet connector
- Failed thermistor
- Bad PCB
How to fix ch series e007 / e008 hot water outlet thermistor - full check: step by step
- Turn off power before unplugging connectors or measuring resistance.
- Check the plug at the sensor and CN13. Dry and fix any wet connector and find the leak.
- Unplug from the PCB and measure: 0.8-20 kOhm is normal. Open or 0 ohm = replace the sensor.
- Note: the manual's wire colours for the supply and DHW sensors are not consistent on these pages, so trace the wire to the sensor before you condemn it.
- If the sensor is good, replace the PCB.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.8 07 Error p.73; 5.9 08 Error p.74. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.