Navien Combi Boiler: CH series E003 ignition failure – full check
CH series E003 ignition failure - full check on a Navien combi boiler: The unit tries to light 10 times. No flame after that = E003, manual reset.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e003 ignition failure - full check
- Gas valve closed or low gas supply / undersized meter or pipe
- Electrode gap wrong, cracked insulator or arcing to the chamber
- Ignition transformer or its 120 V feed
- Main gas valve (no DC power, open coil, stuck solenoid)
- Dirty or bent flame rod, bad ground
- APS hose torn or full of water
- Wrong DIP model setting
- Gas-air differential out of adjustment
- Plugged burner nozzle
- Rainwater in intake / flue
- Bad PCB
How to fix ch series e003 ignition failure - full check: step by step
- Gas work: licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
- Check the gas valve is open. With the boiler at max fire, inlet must be NG 6-10.5 in. W.C. Check dynamic (running) pressure, not just static.
- Gas pipe should be 3/4 in. or larger. Overtightened nuts can push the gasket and choke the flow. Check the meter is big enough for all appliances (example in manual: 425 CFH total).
- Igniter: 97-138 VAC across the two wires of CN17 during ignition. No voltage = PCB.
- Pull the electrode. Gap should be about 3-4 mm. Replace if cracked or out of shape. Check spark-wire boots for cracks.
- Main gas valve: 83-120 VDC on the two brown wires (pins 1-2) of CN15 during ignition. Coil resistance 0.8-2.4 kOhm. You should feel or hear the solenoid click.
- Modulating valve: 2-10 VDC at CN14.
- Flame rod: 10-20 VDC at CN19, flame current 7-20 µA (1-20 µA also given). Clean or replace the rod. Check ground: paint under ground screws can break it, and the outlet must be grounded.
- Check the APS hose for tears or water left from install.
- Check the DIP model setting on the PCB.
- Check the gas-air differential at 3-stage min (see gas-air guide).
- Quick test: cover the blower inlet with your hand during ignition. If it lights, the problem is on the gas supply side.
- Pull the manifold and check the nozzles (stage 1 matters most for lighting).
- Check the intake for collected rainwater (pipe sloped the wrong way).
- If all checks pass, replace the PCB.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.4 03 Error p.61-68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.