Weil-McLain Boiler: Zoning four space heating zones with circulators
Zoning four space heating zones with circulators on a Weil-McLain boiler: Layout for four space heating zones with no indirect DHW, using circulators or 120VAC zone valves. Shown for 110/155 models; 220-399 use the wiring diagram.
Applies to: Evergreen Pro control, four-zone space heating with circulators or 120VAC zone valves
How to fix zoning four space heating zones with circulators: step by step
- Review the 120VAC output wiring and the 24VAC input wiring pages (49 and 50) before connecting anything.
- Wire the four thermostat inputs to J17-1/2, J17-4/5, J17-7/8 and J16-1/2.
- Wire each circulator or zone valve to its matching output. Each circulator output is limited to 2.0 A.
- Choose the space heating system type that matches the system, either in the WIZARD setup or manually in the PRIORITY 2 menu under System Settings.
- Keep the factory default settings for the chosen system type, or change them if the system needs it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.