Weil-McLain Boiler: Zone valve zoning, primary/secondary piping (with optional DHW)
Zone valve zoning, primary/secondary piping (with optional DHW) on a Weil-McLain boiler: Boiler loop is a secondary circuit off the primary system loop. This ensures flow in the boiler loop and keeps the boiler circulator head off the zone valves.
Applies to: SVF 1500-3000 Series 1
How to fix zone valve zoning, primary/secondary piping (with optional dhw): step by step
- Install a system circulator sized for the required flow and head.
- Install a flow/check valve on the boiler outlet piping to stop gravity circulation during DHW heating.
- Use at least the minimum pipe size from Figure 11 on all boiler loop piping.
- Keep primary/secondary tees no more than 8 pipe diameters apart.
- Place system supply and return immersion sensors at least 6 pipe diameters (no more than 3 feet) from the boiler connection tees.
- Wire zone valve end switches to a Space Heating Priority input (default Priority 2).
- Use isolation relays if connecting 3-wire zone valve end switches to the inputs.
- Provide a system expansion tank per page 16. Do not use a closed-type tank if connecting to a water heater with an automatic vent.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.