Weil-McLain Boiler: Zone valve zoning with primary/secondary piping

Updated · by Aurora Star Tech Inc.

Zone valve zoning with primary/secondary piping on a Weil-McLain boiler: Zone valves are used with primary/secondary piping so the boiler loop gets enough flow and the boiler circulator head does not reach the valves.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Zone valve zoned systems

How to fix zone valve zoning with primary/secondary piping: step by step

  1. Pipe the boiler loop with primary/secondary connection tees no more than 12 in. apart.
  2. Keep the boiler loop piping at least the minimum size for the model.
  3. Install isolation valves, purge/drain valves and flow/check valves per the figure.
  4. For a closed-type expansion tank, pipe the tank and make-up water as in the Figure 4 layout.
  5. Strap supply and return sensors to the lines at least 6 pipe diameters, and no more than 3 feet, from the boiler connection tees.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 52. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.