Weil-McLain Boiler: Wiring multiple zones (EG water boilers)
Wiring multiple zones (EG water boilers) on a Weil-McLain boiler: Zone valves or circulators can be used for multiple zones. Each zone needs its own power and control wiring as shown in the wiring diagram. Zoning with circulators needs a relay for each circulator.
Applies to: EG water boilers with Unity-CI control
How to fix wiring multiple zones (eg water boilers): step by step
- Power 3-wire zone valves from a separate transformer. The boiler does not supply that power.
- For circulator zoning, fit one relay per circulator and wire each relay to the matching CH or DHW terminals.
- Do not wire 3-wire zone valve end switches directly to the boiler T-T terminals.
- Wire each zone valve end switch to an isolation relay coil, then wire the isolation relay contact across the boiler T-T terminals.
- Follow the zone valve manufacturer's literature for valve wiring and application.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.