Weil-McLain Boiler: Wiring external limits
Wiring external limits on a Weil-McLain boiler: Two limit types can be wired to J20, depending on whether the boiler should lock out or restart on its own.
Applies to: Evergreen 110/155/220/299/300/399
How to fix wiring external limits: step by step
- Remove the factory jumper at the limit terminals you are using.
- For manual reset, wire isolated limit contacts across J20 pins 1 and 2.
- For automatic reset, wire isolated limit contacts across J20 pins 3 and 4.
- Check the wiring diagram on page 56 for the full layout.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.