Weil-McLain Boiler: Wire thermostats and dry contact inputs
Wire thermostats and dry contact inputs on a Weil-McLain boiler: Inputs are dry contacts only. The boiler does not supply 24V to thermostat circuits.
Applies to: ECO Tec Series 3 all models
How to fix wire thermostats and dry contact inputs: step by step
- Do not supply 24 VAC to the thermostat or input circuits.
- If a thermostat needs continuous 24V power, connect its common wire (C). Keep total draw at or below 120 mA at 24VAC per thermostat.
- For 3-wire zone valves, use relays to give the control dry contacts (the valve end switch carries 24VAC).
- Connect each thermostat or aquastat to its matching input terminal.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.