Weil-McLain Boiler: Wire external limit with manual reset
Wire external limit with manual reset on a Weil-McLain boiler: Control locks out when this limit opens. A technician or operator must reset the control.
Applies to: ECO Tec Series 3 all models
Common causes of wire external limit with manual reset
- External limit opened (for example high limit or other safety device)
How to fix wire external limit with manual reset: step by step
- Remove the factory-installed jumper on J20 pins 1 and 2.
- Connect the isolated contacts of the external limits across J20 pins 1 and 2.
- If the limit opens, the control locks out, activates the alarm terminals, and shuts down the boiler.
- After the limit closes, reset the control manually using the procedure in this manual.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.