Updated · by Aurora Star Tech Inc.

Vertical concentric termination: roof penetration on a Weil-McLain boiler: Prepare the roof opening and thimble before running the termination through it. Follow local codes for isolating vent pipe through floors, ceilings and roofs.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 3 in and 4 in vertical concentric termination

How to fix vertical concentric termination: roof penetration: step by step

  1. For a 3 in termination, cut a 5 in diameter hole to clear the 4-1/2 in outside diameter.
  2. For a 4 in termination, cut a 6-1/2 in diameter hole to clear the 6 in outside diameter.
  3. Insert a galvanized metal thimble in the vent pipe hole.
  4. Install flashing and sealing boots sized for the concentric termination outside diameter.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual, p. 76. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.