Weil-McLain Boiler: Vent material limits and bird screens
Vent material limits and bird screens on a Weil-McLain boiler: Approved vent materials and the screens that must go on each termination.
Applies to: All Ultra vent and air piping
How to fix vent material limits and bird screens: step by step
- Use only the vent and air materials listed in Figure 13. Use only PVC Schedule 40 with concentric terminations; DWV, CPVC and ABS are not allowed there.
- Use locking collars on every joint of polypropylene vent systems.
- Put a bird screen on every vent and air termination. Screens are sold separately and most kits do not include them.
- For flex polypropylene, convert length with the listed equivalent factors (e.g., Duravent 4 in: 3.0 equivalent ft per ft). Keep the total equivalent length within the Figure 12 limits.
- Stainless AL29-4C vent must be installed with the certified manufacturer adapter.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.