Weil-McLain Boiler: Variable speed boiler pump setup (0-10 VDC output)

Updated · by Aurora Star Tech Inc.

Variable speed boiler pump setup (0-10 VDC output) on a Weil-McLain boiler: The 0-10 VDC output drives a variable speed boiler pump. Voltages are set in Manual Test Mode for each firing rate.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Variable speed boiler pump

How to fix variable speed boiler pump setup (0-10 vdc output): step by step

  1. Connect the 0-10 VDC output to the pump's 0-10 VDC input.
  2. Open Contractor menu, Diagnostics, Manual Test Mode.
  3. Highlight FORCE RATE, press EDIT, choose HIGH, then SAVE.
  4. Adjust pump volts until the desired delta T on the boiler is reached, then SAVE AS MAX VOLTS.
  5. Set Pump Volts back to AUTO and repeat for each FORCE RATE speed, including ignition speed.
  6. Confirm operating voltages: VARIABLE SPEED MAX RATE VOLTS, VARIABLE SPEED MIN RATE VOLTS, and VOLTS WHEN BURNER OFF.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Series 2 Advanced Manual, p. 11. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.