Updated · by Aurora Star Tech Inc.

Ultra-399 propane conversion and start-up on a Weil-McLain boiler: The Ultra-399 is converted for propane by adjusting the gas valve throttle screw only; no orifice change. Requires a combustion analyzer.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra-399 propane firing

How to fix ultra-399 propane conversion and start-up: step by step

  1. Before starting, turn the gas valve throttle screw clockwise 5 turns.
  2. Start the boiler following the startup procedure on page 40.
  3. Make slight throttle screw adjustments to reach CO2 of 10.2% with CO below 100 ppm air free. Let the analyzer reading stabilize before each change.
  4. When set correctly, fill in the propane conversion label and attach it to the boiler rating plate.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 gas-fired water boiler manual, p. 41. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.