Weil-McLain Boiler: Two space heating zones using zone valves (no DHW)
Two space heating zones using zone valves (no DHW) on a Weil-McLain boiler: Input 1 runs the system circulator. Zone valve systems need a bypass pressure regulating valve because flow can occur with the valves closed.
Applies to: SVF Series 1 with zone valves
How to fix two space heating zones using zone valves (no dhw): step by step
- Install a bypass pressure regulating valve. Flow can occur with zone valves closed.
- Wire space heating thermostats to Inputs 2 and 3, keeping them on Priority 2.
- Set Priority 2 for the heating system type and confirm RUN AUX PUMP/OUT is YES.
- Assign Input 1 to AUX PUMP/OUTPUT and choose ANY INPUT BY ITS PRIORITY so the system pump runs on any zone call.
- Do not wire a thermostat to P11-4/5 because Input 1 is used for the system circulator.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 67. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.