Weil-McLain Boiler: Thermostat and zone valve wiring
Thermostat and zone valve wiring on a Weil-McLain boiler: Thermostat circuits are dry contacts. Never apply 24VAC to them.
Applies to: Evergreen 110/155/220/299/300/399
How to fix thermostat and zone valve wiring: step by step
- Do not supply 24-volt power to the thermostat circuits or any other application.
- If a thermostat needs continuous 24VAC, connect its common wire ('C') as shown in the wiring diagram.
- Keep the total draw at 120 mA or less at 24VAC per thermostat.
- For 3-wire zone valves, use relays to give the control dry contacts. Valve end switches carry 24VAC from the valve.
- Set the thermostat anticipator to 0.1 A.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.