Updated · by Aurora Star Tech Inc.

Test probe-type low water cutoff on a Weil-McLain boiler: Checks that the probe-type low water cutoff stops firing at low water and allows firing once refilled.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG steam boilers with probe-type LWCO

How to fix test probe-type low water cutoff: step by step

  1. Turn off power to the boiler and wait 5 minutes.
  2. Drain water to the bottom of the gauge glass.
  3. Turn on power.
  4. Set the thermostat to call for heat. The red neon lamp on the lower water cutoff should light.
  5. Wait 5 minutes. The boiler should not fire.
  6. Refill the boiler to the correct waterline. The red lamp should go off.
  7. Wait 5 minutes. The boiler should fire.
  8. Return the thermostat to its normal setting.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 70. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.