Weil-McLain Boiler: Test ignition system safety device (gas shutoff)
Test ignition system safety device (gas shutoff) on a Weil-McLain boiler: Confirms the boiler shuts off gas flow when the main gas supply is cut with the burners on and recovers properly.
Applies to: EG and PEG Series 7 boilers
How to fix test ignition system safety device (gas shutoff): step by step
- Connect a manometer to the outlet side of the gas valve.
- Start the boiler and let the normal start-up cycle run until the main burners ignite.
- With the main burners on, manually shut off the gas supply at the manual main shutoff gas valve.
- Confirm the burners go off and the manometer shows no gas flow.
- Open the manual main shutoff gas valve.
- Confirm the pilot relights, the flame sensing element senses the pilot flame and the main burners reignite.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.