Weil-McLain Boiler: Switching a Weil-McLain oil boiler to B100 biodiesel
Switching a Weil-McLain oil boiler to B100 biodiesel on a Weil-McLain boiler: Notes from the Weil-McLain B100 addendum for Ultra Oil, WGO, WTGO and SGO boilers.
Applies to: Weil-McLain Ultra Oil (UO-3 to UO-5) and WGO/WTGO/SGO (GO-2 to GO-9) oil boilers
Common causes of switching a weil-mclain oil boiler to b100 biodiesel
- Poor cold-weather fuel flow with high blends
- Filter plugging from loosened tank sludge
- Wrong firing rate after the switch
How to fix switching a weil-mclain oil boiler to b100 biodiesel: step by step
- Only UL-approved B100 burners may burn B100. The addendum lists the B100 burner part number for each boiler size.
- Standard #2 oil in Canada (CAN/CGSB-3.2) allows only up to 5% biodiesel. Think about cold-weather fuel properties before going higher.
- Use one-pipe with an oil deaerator and 10 micron filtration. Expect more filter changes early on.
- Before switching, set the burner at 12.25-12.5% CO2 on #2 oil.
- Once on B100, drop pump pressure 6-8 psi to keep the same GPH as #2 oil.
- Use the addendum tables (Beckett and Carlin, #2-B20 vs #2-B100 columns) for nozzle, pump pressure and air settings.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Oil/WGO/WTGO/SGO B100 Biofuel Addendum and Burner Cross Reference Guide 550-143-077/1224, p.1-2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.